Friday, July 28, 2023

JB-QB-FS5101 fire alarm controller

 1. Features of JB-QB-FS5101 fire alarm controller

● 32-bit Cortex-M3 core processor, the system runs at high speed, stable and reliable;

● Support U disk to read/backup programming data, which is convenient for system debugging;

● The fire alarm bus adopts a highly reliable all-digital bus communication protocol, mainly including non-destructive bus information arbitration technology, double verification and real-time interactive verification communication technology, and multi-access cluster automatic ID identification technology;

● Strong EMC anti-interference design and anti-surge design 3 sets of multi-line control output, used to control fire pumps, exhaust fans and other important fire-fighting equipment;

● Event "black box", which can record more than 10,000 events, and will not be lost when power off;

● With powerful self-adaptation and self-diagnosis functions, it is convenient for engineering debugging, bus fault analysis and daily maintenance;

● Applicable to various small industrial and civil buildings such as hotels, residences, industrial plants, and entertainment venues.
2. Technical parameters of JB-QB-FS5101 fire alarm controller
Implementation standard GB4717-2005 "Fire Alarm Controller"
Structural form Wall-mounted, L385mm×W285mm×H85mm
Main power supply AC187V~242V, 50Hz (±1Hz)
Backup power supply DC12V3Ah lead-acid battery two
Switching power supply DC30V 2.3A power supply
Bus parameters Bus voltage: 18V ~ 30V Drive current: 500mA
Bus 1.5km (cross-sectional area ≥ 1.5mm2)
Capacity: 250 points per circuit
Controlled 24V DC24V 500mA
Output interface Fire alarm relay, fault relay
Printer Micro thermal printer
Weight 7.0kg
Expansion interface Optional expansion card (CAN networking and RS485, 4G or Ethernet)
Operating environment 10℃~50℃, -20℃~60℃10RH%-95%RH (no condensation)