JTGB-UF-XSS667 Point Infrared Flame Detector

 1. Overview of JTGB-UF-XSS667 point infrared flame detector

JTGB-UF-XSS667 point-type infrared flame detector is an infrared flame detector specially used for tunnel fire detection. It is based on the characteristic infrared rays emitted by the detection of flames, and processes various parameters sampled from the scene through advanced intelligent algorithms. Later, it is judged whether the fire exists. Compared with other flame detectors, its response speed is fast, its reliability is high and its judgment is accurate.
2. Technical conditions of JTGB-UF-XSS667 point infrared flame detector

Model JTGB-UF-XSS667
Detection angle of view within 180°
Indicator light The green light is flashing for normal, and the red light is always on after an alarm
Response time ≤10 seconds
Working wavelength 3.5μm~5.0μm
Light channel detection Continuous light channel detection, when the transmittance of the window glass drops below 50%, a fault signal is sent, and the fault is automatically restored after the pollution is removed
Working voltage 24VDC
Ambient temperature -40℃~85℃
Ambient humidity 5%~95%RH (no condensation)
Alarm current 55mA
Quiescent current 45mA
Standard output mode Alarm relay contact output, fault relay contact output
Optional output mode Early warning relay contact output, 4 ~ 20mA, RS485 standard interface output: MODBUSRTU
Sensitivity setting Level I 25m (detection is 33cm×33cm×5cm ethanol open flame)
Protection class IP66
Dimensions 180mm×80mm×125mm
Comply with the standards GB15631-2008 "Special Fire Detectors" and GB4208-2008 "Enclosure Protection Level (IP Code)"

Remarks: 1. JTGB-UF-XSS667 point-type infrared flame detector is suitable for detection of smokeless liquid and gas fires and open flame fires that produce smoke, such as open flame combustion of carbon-containing materials (wood, plastic, alcohol, oil products, gas, etc.) wait).
2. Not applicable to the detection of combustion of certain chemical substances (such as phosphorus, sodium, magnesium, sulfur, hydrogen, etc.).
3. If the smoke at the fire scene is so heavy that the detector's field of view is blocked, it will also affect the alarm sensitivity of the flame detector.
4. The detector must be installed with a sunshade when it is installed under outdoor sunlight.
3. Dimensions of JTGB-UF-XSS667 point infrared flame detector

 JTGB-UF-XSS667点型红外火焰探测器外形尺寸图

JTG-HM-FDF241 infrared flame detector FM certification

 1. Overview of JTG-HM-FDF241 infrared flame detector

The JTG-HM-FDF241 infrared flame detector meets the relevant requirements of the national standard GB15631-1995 "point type infrared flame detector". The detector adopts a special fuzzy algorithm, the latest harmonic analysis function and targeted application algorithm, making it very ability to resist false positives.
2. Technical parameters of JTG-HM-FDF241 infrared flame detector

Model JTG-HM-FDF241
Working voltage (addressable working mode) (normal) 12-33 VDC
Working current (addressing mode) (normal) 0.7mA
Working voltage (collective working mode) (normal) 14-28VDC
Working current (collective working mode) (normal) 0.5mA
The maximum number of programmable remote reaction indicators (AI) that can be connected is 2
Working temperature -35-+70℃
Storage temperature -40-+75℃
Humidity (no heavy condensation on sensor window)

≥95% relative humidity when T=25±3℃

93% relative humidity when T=40±2℃
Communication protocol FDnet or collective
Terminal 0.2-1.5mm2
Dimensions 135x135x77
Color pure white (RAL9010)
Protection class IP67

3. Characteristics of JTG-HM-FDF241 infrared flame detector

●JTG-HM-FDF241 infrared flame detector with three sensors

Two sensors detect different wavelengths of light (4...4.8μm and 5.1...6μm)

●The third sensor is used to enhance the anti-interference ability to sunlight (0.7…1.1μm)

●Strong resistance to electromagnetic interference, sunlight and heat radiation, moisture and corrosion

Wide range of viewing angles (minimum 90°)

●Signal processing based on ASAtechnologyTM (Advanced Signal Analysis Technology)

●Built-in short-circuit isolator
4. Applicable places of JTG-HM-FDF241 infrared flame detector

JTG-HM-FDF241 Infrared Flame Detector can be used indoors or outdoors to detect smokeless fires produced by flammable liquids and gases as well as smoked fires produced by carbonaceous substances such as wood, plastics, gas, petroleum products, etc.

JTGB-UF-XSS665 infrared multi-parameter flame detector

 1. Overview of JTGB-UF-XSS665 infrared multi-parameter flame detector:

     JTGB-UF-XSS665 infrared multi-parameter flame detector is an industrial explosion-proof product. It is based on the characteristic infrared rays emitted by the detection flame, and processes various parameters sampled from the scene with advanced intelligent algorithms to determine whether the fire exists. Compared with other flame detectors, it has fast response speed, high reliability and accurate judgment. It is suitable for fire detection and alarm in the open flame stage in flammable and explosive environments, especially suitable for detecting the combustion of organic matter, and can be widely used in traffic tunnels, petrochemical enterprises, papermaking, steel mills, nuclear power plants, power plants, food processing enterprises, military enterprises, etc. .
 
2. Technical conditions of JTGB-UF-XSS665 infrared multi-parameter flame detector:

1. Detection angle of view: within 110°
2. Response time: ≤10 seconds
3. Working wavelength: a band of 3.8μm
4. Two-band 4.4μm
5. Three-band 4.5μm ~ 11μm
6. Working voltage: 24V DC
7. Ambient temperature: -40℃~85℃
8. Ambient humidity: 5%~95%RH (no condensation)
9. Alarm current: 25mA
10. Static current: 18mA
11. Output mode: standard output mode: alarm relay contact output, fault relay contact output;
12. Optional output mode: early warning relay contact output, 4~20mA, RS485 standard interface output: MODBUS RTU
13. Sensitivity setting: Class I 25m (detection is 33cm×33cm×5 cm ethanol open flame)
14. Explosion-proof grade: ExdIICT6 (without acetylene)
15. Protection level: IP66
16. Dimensions: 180mm×80mm×125mm
17. Cable outlet thread: NPT 3/4 pipe thread
18. Compliant with standards: GB15631-2008 "Special Fire Detectors", GB3836.1-2000 "Electrical Equipment for Explosive Gas Atmospheres Part I: General Requirements", GB3836.2-2000 "Electrical Equipment for Explosive Gas Atmospheres Part II: Isolation Explosion type "d"", and GB4208-2008 "Enclosure Protection Level (IP Code)"
Remarks: 1. JTGB-UF-XSS665 point-type infrared flame detector is suitable for detection of smokeless liquid and gas fires and open flame fires that produce smoke, such as open flame combustion of carbon-containing materials (wood, plastic, alcohol, oil products, gas, etc.) wait).
2. Not applicable to the detection of combustion of certain chemical substances (such as phosphorus, sodium, magnesium, sulfur, hydrogen, etc.).
3. If the smoke at the fire scene is so heavy that the detector's field of view is blocked, it will also affect the alarm sensitivity of the flame detector.
4. The detector must be installed with a sunshade when it is installed under outdoor sunlight.
 
3. Basic functions of JTGB-UF-XSS665 infrared multi-parameter flame detector:

     JTGB-UF-XSS665 infrared multi-parameter flame detector is used in places with relatively high safety level. Compared with traditional point-type infrared flame detector products, this product has the characteristics of fast response, accurate judgment, high reliability, and strong anti-false alarm ability.

A715/IR3 Point Infrared Flame Detector Three-Band Infrared

 1. Function and composition of A715/IR3 point infrared flame detector

A715/IR3 point-type infrared flame detector can be used in places where flames (including partial smoldering fires) need to be monitored, quickly discovering flames that may cause fires, and issuing fire alarms in time.

A715/IR3 infrared flame detector converts flame combustion parameters into electrical signals through three infrared pyroelectric sensors working in different bands, and inputs the signals into industrial computing chips for comparison, calculation and analysis processing, and cooperates with special intelligent control software. Fire alarms are issued quickly and accurately.

The A715/IR3 infrared flame detector adopts a special aluminum die-cast flameproof housing, which has good explosion-proof and protective characteristics, corrosion resistance and aging resistance, and can work indoors, outdoors and various special industrial places for a long time.
2. A715/IR3 point type infrared flame detector shape structure and size

In order to meet the detector's long-term stable operation and explosion-proof requirements, the A715/IR3 uses an aluminum die-casting shell. The casing is divided into a shell and a bottom cover.

In order to ensure the explosion-proof performance, the shell and the bottom cover are connected by threads, and a rubber sealing ring is installed on the connection surface.

Both the wire inlet hole and the installation hook are set on the shell to facilitate the wiring operation.

A plastic inner shell is used to fix and protect the circuit part. Only three infrared flame sensors and indicator lights are exposed on the front panel of the inner shell, and only the wiring terminals are exposed at the rear to prevent damage to the circuit during installation and wiring.


 
3. Technical parameters of A715/IR3 infrared flame detector

1. Basic parameters of A715/IR3 point infrared flame detector

Item Specifications
Name Point Infrared Flame Detector
Model A715/IR3
Executive standard GB15631-2008 "Special Fire Detector"
●GB3836.1-2000 "Electrical Equipment for Explosive Gas Atmospheres" Part 1: General Technical Requirements
●GB3836.2-2000 "Electrical Equipment for Explosive Gas Atmospheres" Part 2: Flameproof "D"
Sensors Sharp Detection AE-S708/3, AE-S708/4 and AE-S708/5 Infrared Pyroelectric Sensors
Optical window white sapphire (Al2O3)
Housing ●Material: Aluminum alloy
●Molding process: Die casting
●Coating process: surface electrostatic powder spraying, internal metal passivation treatment
Weight ≤1kg
Explosion-proof and protection Explosion-proof: EXdⅡCT6
●Protection: IP66

2. Working parameters of A715/IR3 point infrared flame detector

Item Specification or Status
Power Supply Minimum Standard Maximum
18VDC (customizable 12VDC) 24VDC 30VDC
Working current Monitoring state ≤ 15mA, alarm state ≤ 35mA
Warm-up time 60s after power on
Fire alarm When a flame (including partial ignition fire) is found in the monitored area, the detector enters the fire alarm state;
The fire alarm output relay acts, and the red fire alarm indicator lights up
Fault alarm When the sensor, power supply, etc. are found to be abnormal, the detector enters the fault alarm state;
The fault output relay acts, and the yellow fault indicator lights up;
When fire alarm and fault occur at the same time, fire alarm takes priority;
Alarm threshold 1-5 levels adjustable (factory set to 3 levels)
The number of times the green light flashes each time in the monitoring state indicates the alarm threshold
Alarm delay 0-30s adjustable (factory set to 0s)
Drift compensation sensor hardware compensation and intelligent software compensation combined mode
It can effectively compensate the drift caused by temperature, environmental changes and long-term work of components
Interference source suppression Can effectively suppress the influence of non-flame interference sources, such as sunlight (direct and reflected), common artificial light sources, background radiation sources, hot moving objects, electric welding, etc.
Indicator light Monitoring status: green light flashing
●Fire alarm status: the red light is always on
●Fault status: the yellow light is always on
Output Fire alarm relay, action when alarming, output contact 1A@30VDC1A@250VAC
●Fault relay, action when fault occurs, output contact 1A@30VDC1A@250VAC
●4-20mA current loop
●Serial communication interface

4. Detection performance and protection range of A715/IR3 infrared flame detector

Maximum detection distance D(max)
Fire source situation A715/IR3 red ultraviolet flame detector maximum detection distance D(max)
Gasoline 0.1㎡ fire plate (0.3m*0.3m)

55m
n-heptane

55m
diesel fuel     

50m
kerosene

50m
aviation kerosene

50m
Alcohol     

50m
Isopropanone

50m
Methanol 45m
Polypropylene 20m
Paper 35m
Methane 0.5m(H)*0.2(w) gas flame 35m
LPG propane

  illustrate:

1. The central axis in the above figure is perpendicular to the detection window;

2. The vertical and horizontal directions of the detection area in the "Schematic Diagram of Detection Area" are consistent;

3. The above figure shows that the 100% position is the maximum detection distance D(max), and the detection distance of each angle can be obtained from the figure

4. Calculated by multiplying the percentage of the upper black edge by D(max);

5. The maximum detection distance D(max) in various environments is detailed in the above table
5. Environmental parameters of A715/IR3 point infrared flame detector

Item Specifications
Working temperature -10℃~+55℃
Working humidity ≤95%HR, no condensation
Storage temperature -20℃~+60℃

6. Setting and recording

Project Description
Setting Using PC and special software, the alarm parameters of the detector can be set through the serial communication port:
●Alarm mode
●Alarm threshold
●Alarm delay time
Professional operation and password authorization are required
Easy setting Use the magnet at hand to control the built-in reed switch to adjust the alarm sensitivity
Record query Using PC and special software, the internal record of the detector can be queried through the serial communication port
●Factory settings: alarm threshold, delay time.
●User settings (default factory settings): alarm threshold, alarm delay time.
●Factory functions: maintenance, calibration, compensation parameter information, qualified identification, software version, product ID, etc.
Professional operation and password authorization are required

7. Main circuit and software of A715/IR3 point infrared flame detector

The circuit part mainly includes sensors, low-noise amplifiers, industrial processing units, peripheral input and output and drive circuits, power supplies and EMC circuits, etc.


The MCU has built-in special software program, which uses Anyu's three-band infrared flame detection algorithm and criterion rules.

JTG-UM-GST9616 Flameproof Infrared Flame Detector

 1. Overview of JTG-UM-GST9616 point infrared flame detector:

JTG-UM-GST9616 point-type infrared flame detector (hereinafter referred to as the detector) is a compound infrared flame detector, which can judge the fire by detecting the light signal of the flame in the two bands of the infrared light region.

The detector is suitable for detecting the burning of open flames produced by carbonaceous materials. It is used in large spaces where flames are the main source of fire at the initial stage. It can be used indoors or outdoors.

This detector will not cause false alarms for interference from sunlight, artificial light sources, heat radiation, etc., and the work is stable and reliable.

The JTG-UM-GST9616 detector has two working modes: coded and non-coded. When working in coding mode, the detector can be directly connected to the fire alarm controller produced by Gulf Company in the form of a bus, and the detector obtains power from the bus and transmits information through the bus. When working in non-coding mode, the detector needs DC24V power supply to transmit information through the relay contacts.

This detector is an explosion-proof product, which can be used in general civil places and industrial hazardous places, such as Zone 1 and Zone 2 in explosive gas environments and Zone 21 and Zone 22 in combustible dust places.
2. Technical characteristics of JTG-UM-GST9616 point infrared flame detector:

1. Working voltage:

Coding mode: bus power supply, voltage range: DC16V ~ DC28V

Non-coding mode: DC24V power supply, voltage range: DC20V~DC28V

2. Working current:

Encoding mode: monitoring current ≤ 2mA, alarm current ≤ 4mA;

Non-coding mode: monitoring current ≤ 19mA, alarm current ≤ 35mA

3. Sensitivity level:

The detector has three sensitivity levels, which meet the requirements of GB15631-1995.

The factory setting of the detector is Class I sensitivity, which is the highest sensitivity. Users can reduce the sensitivity level according to the needs of the site. The sensitivity level of the detector can be changed on site by using the electronic encoder produced by Gulf Company.

4. Detection range:

The furthest detection distance of the detector corresponds to a level I sensitivity of 25m, a level II sensitivity of 17m, and a level III sensitivity of 12m. The corresponding relationship between detection distance and angle is shown in Figure 1, and the shaded part is the detectable range. The semicircle in the figure represents the detection distance, which is given as a percentage.


5. Response time ≤30s;

6. Indicator lights:

Red LED: Periodically flashes when in monitoring status, and keeps on when in fire alarm;

Yellow LED: off when monitoring status, always on when fault occurs;

7. Contact output:

1) When the detector works in encoding mode, the contact output is not used, and the contact signal is invalid.

2) When the detector works in non-coding mode, it has fire alarm contact output and fault contact output.

Fire alarm contact output: passive normally open contact, contact capacity is 1A/30VDC;

Fault contact output: passive normally open contact, contact capacity 1A/30VDC.

8. Use environment:

Temperature: -20℃~+55℃

Relative humidity: ≤95%, non-condensing

9. Protection level: IP66

10. Dimensions: 166mm×235mm×199mm (with adjustment frame)

11. Installation hole distance: 125.5mm×80mm

12. Shell material and color: stainless steel, metallic gray

13. Cable requirements:

1) Coding mode: connect to the controller bus, use RVS twisted pair with core section ≥ 1.0mm2;

2) Non-coding mode: Connect with DC24V power supply, use cables with core cross-section ≥ 1.0mm2, cable outer diameter of 8mm ~ 10mm, it is recommended to use cables with copper core multi-strand conductors;

3) It should meet the requirements of the use environment, such as explosion-proof, heat-resistant, corrosion-resistant, fire-resistant, etc.

14. Weight:

Detector 4.8kg

Adjustment frame 1.3kg

15. Explosion-proof mark: ExdIICT6/DIPA21TA, T6 explosion-proof certificate number: CNEx06.0429

16. Executive standard: GB3836.1-2000, GB3836.2-2000, GB12476.1-2000, GB15631-1995
3. Test of JTG-UM-GST9616 point infrared flame detector:

Warning: Please wait until all the detectors are installed before turning on the power, and then test after working for 60 seconds.

1. The detector must be tested after installation or after each regular maintenance.

2. Test content:

1) The detector in encoding mode should be able to be registered by the controller after it is powered on; the red indicator light should flash periodically when it is in the monitoring state; after the detector is powered on for 20 minutes, it will light up the infrared light at a distance of about 1.5m in front of it. The light source and the detector should alarm and light the fire indicator light within 30s; the controller can reset the detector to return to the normal monitoring state.

2) For detectors in non-coding mode, the red indicator light should flash periodically when it is powered on and in the monitoring state; after the detector is powered on for 20 minutes, ignite the infrared light source at a distance of about 1.5m in front of it, and the detector should transmit within 30s The fire alarm contact signal is issued and the fire alarm indicator light is lit.

3. For detectors in encoding mode, after the test, the controller sends a communication command to reset the detector and notify the relevant management department that the system returns to normal.

4. For detectors in non-standard mode, after the test, the power is cut off directly, and the relevant management department is notified that the system returns to normal.

5. During the test, the unqualified detectors should be cleaned according to "Maintenance" and then tested again. If they still fail to pass the test, they should be returned for repair.

JTH-CH381Ex point type infrared flame detector (three wavelengths)

 1. Performance characteristics of JTH-CH381Ex point infrared flame detector

Immunity to electromagnetic radiation, sunlight and background thermal radiation.

3.8uM, 4.4uM, 5.0-11.0uM three wavelength detection reduces false explosion rate.

Standard RS485 interface based on Modbus (RTU) protocol and 4~20mA output, alarm relay output.

It can be used in conjunction with the alarm controller, PLC, DCS and other systems produced by Xihe Caiqiao.

It adopts single-chip microcomputer processing system, which has strong stability and anti-interference ability and low power consumption.

Reverse protection function.
2. Technical parameters of JTH-CH381Ex point infrared flame detector
Model JTH-CH381Ex
Name Point Infrared Flame Detector
Brand Xihe Caiqiao
Spectral range 3.8um 4.4um 5.0um
Fire Sensitivity Level Ⅰ
Detection angle ≤120°
Rotation angle 180°
Signal transmission mode 4-20mA output, standard RS485 interface, alarm relay output
Working voltage 16~32VDC (rated: 24VDC)
Power consumption <2W
Temperature range -10℃~+55℃
Humidity range 0~95﹪RH (no condensation)
Pressure range 86KPa~106KPa
Shell material cast aluminum
Machine weight 1.6Kg
Protection class IP66
Mounting thread G3/4"
Dimensions 186mm*191mm*96mm
3. Installation and wiring of JTH-CH381Ex point infrared flame detector

 JTH-CH381Ex点型红外火焰探测器安装

VFD/S-LA880 optical section smoke detector linear beam infrared beam

 1. Overview of VFD/S-LA880 optical section smoke detector

Linear beam smoke detector (also known as optical cross-section smoke detector, divided into visualization and standard type, this model is the standard type) is an intelligent smoke detector, which uses optical cross-section image smoke detection Detection technology, consisting of transmitters and receivers, each receiver can correspond to multiple transmitters (the number of transmitters is determined according to the site conditions), can implement arbitrary curved surface coverage for the protected space, and has the ability to distinguish emission light sources and interference light sources Ability. It is composed of an image acquisition unit, an embedded intelligent fire analysis platform, etc., and realizes functions such as video acquisition, fire analysis, fire alarm, fault alarm, and video encoding transmission. Communication with the monitoring center through optical fiber Ethernet realizes intelligent analysis, distributed detection, networked transmission and centralized management. It is suitable for special places with large spaces such as tobacco warehouses, railway stations, and exhibition centers.
2. Functional characteristics of VFD/S-LA880 optical section smoke detector

Embedded intelligent fire analysis platform is adopted to realize distributed fire detection and centralized management;

Adopt image non-contact smoke detection, with long detection distance and large protection area;

Each receiver can correspond to multiple transmitters, and any curved surface coverage can be implemented for the protected area;

Adjustable multi-level sensitivity, strong environmental applicability, and anti-vibration interference ability;

Industrial appearance design, protection level up to IP65;

Strong compatibility, can be connected to conventional automatic fire alarm system;

Simple structure, easy maintenance and strong scalability.
3. Application places of VFD/S-LA880 optical section smoke detector

Exhibition Center, Conference Center

Airport terminals, railway waiting halls, hangars, moving garages

Gymnasium, sports center, theater

commercial atrium

Comprehensive pipe gallery, highway tunnel, industrial plant

Warehousing and logistics center

...
4. Technical parameters of VFD/S-LA880 optical section smoke detector

Optical section fire detector receiver technical parameters
Model VFD/S-LA880/R
Working voltage DC24 V±15%
Rated power ≤20W
Communication interface RJ45
Protection angle (H×V) 64°×50°
Detection distance 3~30m
Switch output: 1 fire alarm, 1 failure
Digital input 1 reset signal
Video resolution D1 (720×576), H.264
Support protocols TCP/IP, HTTP, RTSP
Working temperature -10℃~55℃
Working humidity ≤93%RH(40℃)
Air pressure 80KPa~106KPa
Dimensions 249 (length) × 158 (width) × 80 (height) (mm)
Weight 1.75Kg
Shell material aluminum alloy
Protection class IP65
Installation method wall mount, ceiling mount

Light section fire detector transmitter technical parameters
Model VFD/S-LA880/T
Working voltage DC24 V±15%
Rated power ≤5W
Working temperature -10℃~55℃
Working humidity ≤93%RH(40℃)
Air pressure 80KPa~106KPa
Dimensions 66 (L) × 106 (W) × 138 (H) (mm)
Weight 0.30Kg
Shell material ABS
Protection class IP65
Installation method wall mount, ceiling mount

JTY-HM-TX3703 Linear Beam Smoke Detector

 1. Overview of JTY-HM-TX3703 linear beam smoke detector

JTY-HM-TX3703 linear beam smoke detector is a coded reflective linear infrared beam smoke detector, and the detector must be used with a reflector.

The detector adopts a new and reasonable structural design, and is equipped with a unique laser module and digital tube indication during the debugging process, making the debugging process simpler. The detector can be used in shopping malls, fitness centers, gymnasiums, exhibition halls, museums, hotel lobbies, printing factories, garment factories, warehouses and other places.
2. Working principle of JTY-HM-TX3703 linear beam smoke detector

The detector is placed opposite to the reflector. The detector consists of two parts: transmitting and receiving. The transmitting part emits an infrared beam of a certain intensity. After being reflected by the reflector, the receiving part of the detector synchronously collects and amplifies the returned infrared beam, and the collected signal is processed by the built-in single-chip microcomputer. Analyze and judge. When the smoke enters the detection area, the intensity of the infrared light received by the receiving part decreases because the smoke blocks the light. After reaching the alarm threshold, the detector lights up the red indicator light and uploads the fire alarm signal through the bus.
3. Functional characteristics of JTY-HM-TX3703 linear beam smoke detector

Communication method: non-polar two bus

With automatic compensation function, it can automatically compensate for the influence caused by factors such as dust and vibration to a certain extent, which improves the reliability of the detector

Debugging is simple, there is a concentric laser module indication, you can easily find the optical path, and there is a digital tube display, which can indicate the intensity of reflected light

Sensitivity and distance values can be set on site through the hand-held encoder

Fully sealed protection process of PCB board

Support two application modes of coding and non-coding