1. Performance characteristics of JTH-CH381Ex point infrared flame detector
Immunity to electromagnetic radiation, sunlight and background thermal radiation.
3.8uM, 4.4uM, 5.0-11.0uM three wavelength detection reduces false explosion rate.
Standard RS485 interface based on Modbus (RTU) protocol and 4~20mA output, alarm relay output.
It can be used in conjunction with the alarm controller, PLC, DCS and other systems produced by Xihe Caiqiao.
It adopts single-chip microcomputer processing system, which has strong stability and anti-interference ability and low power consumption.
Reverse protection function.
2. Technical parameters of JTH-CH381Ex point infrared flame detector
Model JTH-CH381Ex
Name Point Infrared Flame Detector
Brand Xihe Caiqiao
Spectral range 3.8um 4.4um 5.0um
Fire Sensitivity Level Ⅰ
Detection angle ≤120°
Rotation angle 180°
Signal transmission mode 4-20mA output, standard RS485 interface, alarm relay output
Working voltage 16~32VDC (rated: 24VDC)
Power consumption <2W
Temperature range -10℃~+55℃
Humidity range 0~95﹪RH (no condensation)
Pressure range 86KPa~106KPa
Shell material cast aluminum
Machine weight 1.6Kg
Protection class IP66
Mounting thread G3/4"
Dimensions 186mm*191mm*96mm
3. Installation and wiring of JTH-CH381Ex point infrared flame detector