1. Overview of VFD/S-LA880 optical section smoke detector
Linear beam smoke detector (also known as optical cross-section smoke detector, divided into visualization and standard type, this model is the standard type) is an intelligent smoke detector, which uses optical cross-section image smoke detection Detection technology, consisting of transmitters and receivers, each receiver can correspond to multiple transmitters (the number of transmitters is determined according to the site conditions), can implement arbitrary curved surface coverage for the protected space, and has the ability to distinguish emission light sources and interference light sources Ability. It is composed of an image acquisition unit, an embedded intelligent fire analysis platform, etc., and realizes functions such as video acquisition, fire analysis, fire alarm, fault alarm, and video encoding transmission. Communication with the monitoring center through optical fiber Ethernet realizes intelligent analysis, distributed detection, networked transmission and centralized management. It is suitable for special places with large spaces such as tobacco warehouses, railway stations, and exhibition centers.
2. Functional characteristics of VFD/S-LA880 optical section smoke detector
Embedded intelligent fire analysis platform is adopted to realize distributed fire detection and centralized management;
Adopt image non-contact smoke detection, with long detection distance and large protection area;
Each receiver can correspond to multiple transmitters, and any curved surface coverage can be implemented for the protected area;
Adjustable multi-level sensitivity, strong environmental applicability, and anti-vibration interference ability;
Industrial appearance design, protection level up to IP65;
Strong compatibility, can be connected to conventional automatic fire alarm system;
Simple structure, easy maintenance and strong scalability.
3. Application places of VFD/S-LA880 optical section smoke detector
Exhibition Center, Conference Center
Airport terminals, railway waiting halls, hangars, moving garages
Gymnasium, sports center, theater
commercial atrium
Comprehensive pipe gallery, highway tunnel, industrial plant
Warehousing and logistics center
...
4. Technical parameters of VFD/S-LA880 optical section smoke detector
Optical section fire detector receiver technical parameters
Model VFD/S-LA880/R
Working voltage DC24 V±15%
Rated power ≤20W
Communication interface RJ45
Protection angle (H×V) 64°×50°
Detection distance 3~30m
Switch output: 1 fire alarm, 1 failure
Digital input 1 reset signal
Video resolution D1 (720×576), H.264
Support protocols TCP/IP, HTTP, RTSP
Working temperature -10℃~55℃
Working humidity ≤93%RH(40℃)
Air pressure 80KPa~106KPa
Dimensions 249 (length) × 158 (width) × 80 (height) (mm)
Weight 1.75Kg
Shell material aluminum alloy
Protection class IP65
Installation method wall mount, ceiling mount
Light section fire detector transmitter technical parameters
Model VFD/S-LA880/T
Working voltage DC24 V±15%
Rated power ≤5W
Working temperature -10℃~55℃
Working humidity ≤93%RH(40℃)
Air pressure 80KPa~106KPa
Dimensions 66 (L) × 106 (W) × 138 (H) (mm)
Weight 0.30Kg
Shell material ABS
Protection class IP65
Installation method wall mount, ceiling mount