JTGB-UF-XSS667 Point Infrared Flame Detector

 1. Overview of JTGB-UF-XSS667 point infrared flame detector

JTGB-UF-XSS667 point-type infrared flame detector is an infrared flame detector specially used for tunnel fire detection. It is based on the characteristic infrared rays emitted by the detection of flames, and processes various parameters sampled from the scene through advanced intelligent algorithms. Later, it is judged whether the fire exists. Compared with other flame detectors, its response speed is fast, its reliability is high and its judgment is accurate.
2. Technical conditions of JTGB-UF-XSS667 point infrared flame detector

Model JTGB-UF-XSS667
Detection angle of view within 180°
Indicator light The green light is flashing for normal, and the red light is always on after an alarm
Response time ≤10 seconds
Working wavelength 3.5μm~5.0μm
Light channel detection Continuous light channel detection, when the transmittance of the window glass drops below 50%, a fault signal is sent, and the fault is automatically restored after the pollution is removed
Working voltage 24VDC
Ambient temperature -40℃~85℃
Ambient humidity 5%~95%RH (no condensation)
Alarm current 55mA
Quiescent current 45mA
Standard output mode Alarm relay contact output, fault relay contact output
Optional output mode Early warning relay contact output, 4 ~ 20mA, RS485 standard interface output: MODBUSRTU
Sensitivity setting Level I 25m (detection is 33cm×33cm×5cm ethanol open flame)
Protection class IP66
Dimensions 180mm×80mm×125mm
Comply with the standards GB15631-2008 "Special Fire Detectors" and GB4208-2008 "Enclosure Protection Level (IP Code)"

Remarks: 1. JTGB-UF-XSS667 point-type infrared flame detector is suitable for detection of smokeless liquid and gas fires and open flame fires that produce smoke, such as open flame combustion of carbon-containing materials (wood, plastic, alcohol, oil products, gas, etc.) wait).
2. Not applicable to the detection of combustion of certain chemical substances (such as phosphorus, sodium, magnesium, sulfur, hydrogen, etc.).
3. If the smoke at the fire scene is so heavy that the detector's field of view is blocked, it will also affect the alarm sensitivity of the flame detector.
4. The detector must be installed with a sunshade when it is installed under outdoor sunlight.
3. Dimensions of JTGB-UF-XSS667 point infrared flame detector

 JTGB-UF-XSS667点型红外火焰探测器外形尺寸图

JTG-HM-FDF241 infrared flame detector FM certification

 1. Overview of JTG-HM-FDF241 infrared flame detector

The JTG-HM-FDF241 infrared flame detector meets the relevant requirements of the national standard GB15631-1995 "point type infrared flame detector". The detector adopts a special fuzzy algorithm, the latest harmonic analysis function and targeted application algorithm, making it very ability to resist false positives.
2. Technical parameters of JTG-HM-FDF241 infrared flame detector

Model JTG-HM-FDF241
Working voltage (addressable working mode) (normal) 12-33 VDC
Working current (addressing mode) (normal) 0.7mA
Working voltage (collective working mode) (normal) 14-28VDC
Working current (collective working mode) (normal) 0.5mA
The maximum number of programmable remote reaction indicators (AI) that can be connected is 2
Working temperature -35-+70℃
Storage temperature -40-+75℃
Humidity (no heavy condensation on sensor window)

≥95% relative humidity when T=25±3℃

93% relative humidity when T=40±2℃
Communication protocol FDnet or collective
Terminal 0.2-1.5mm2
Dimensions 135x135x77
Color pure white (RAL9010)
Protection class IP67

3. Characteristics of JTG-HM-FDF241 infrared flame detector

●JTG-HM-FDF241 infrared flame detector with three sensors

Two sensors detect different wavelengths of light (4...4.8μm and 5.1...6μm)

●The third sensor is used to enhance the anti-interference ability to sunlight (0.7…1.1μm)

●Strong resistance to electromagnetic interference, sunlight and heat radiation, moisture and corrosion

Wide range of viewing angles (minimum 90°)

●Signal processing based on ASAtechnologyTM (Advanced Signal Analysis Technology)

●Built-in short-circuit isolator
4. Applicable places of JTG-HM-FDF241 infrared flame detector

JTG-HM-FDF241 Infrared Flame Detector can be used indoors or outdoors to detect smokeless fires produced by flammable liquids and gases as well as smoked fires produced by carbonaceous substances such as wood, plastics, gas, petroleum products, etc.

JTGB-UF-XSS665 infrared multi-parameter flame detector

 1. Overview of JTGB-UF-XSS665 infrared multi-parameter flame detector:

     JTGB-UF-XSS665 infrared multi-parameter flame detector is an industrial explosion-proof product. It is based on the characteristic infrared rays emitted by the detection flame, and processes various parameters sampled from the scene with advanced intelligent algorithms to determine whether the fire exists. Compared with other flame detectors, it has fast response speed, high reliability and accurate judgment. It is suitable for fire detection and alarm in the open flame stage in flammable and explosive environments, especially suitable for detecting the combustion of organic matter, and can be widely used in traffic tunnels, petrochemical enterprises, papermaking, steel mills, nuclear power plants, power plants, food processing enterprises, military enterprises, etc. .
 
2. Technical conditions of JTGB-UF-XSS665 infrared multi-parameter flame detector:

1. Detection angle of view: within 110°
2. Response time: ≤10 seconds
3. Working wavelength: a band of 3.8μm
4. Two-band 4.4μm
5. Three-band 4.5μm ~ 11μm
6. Working voltage: 24V DC
7. Ambient temperature: -40℃~85℃
8. Ambient humidity: 5%~95%RH (no condensation)
9. Alarm current: 25mA
10. Static current: 18mA
11. Output mode: standard output mode: alarm relay contact output, fault relay contact output;
12. Optional output mode: early warning relay contact output, 4~20mA, RS485 standard interface output: MODBUS RTU
13. Sensitivity setting: Class I 25m (detection is 33cm×33cm×5 cm ethanol open flame)
14. Explosion-proof grade: ExdIICT6 (without acetylene)
15. Protection level: IP66
16. Dimensions: 180mm×80mm×125mm
17. Cable outlet thread: NPT 3/4 pipe thread
18. Compliant with standards: GB15631-2008 "Special Fire Detectors", GB3836.1-2000 "Electrical Equipment for Explosive Gas Atmospheres Part I: General Requirements", GB3836.2-2000 "Electrical Equipment for Explosive Gas Atmospheres Part II: Isolation Explosion type "d"", and GB4208-2008 "Enclosure Protection Level (IP Code)"
Remarks: 1. JTGB-UF-XSS665 point-type infrared flame detector is suitable for detection of smokeless liquid and gas fires and open flame fires that produce smoke, such as open flame combustion of carbon-containing materials (wood, plastic, alcohol, oil products, gas, etc.) wait).
2. Not applicable to the detection of combustion of certain chemical substances (such as phosphorus, sodium, magnesium, sulfur, hydrogen, etc.).
3. If the smoke at the fire scene is so heavy that the detector's field of view is blocked, it will also affect the alarm sensitivity of the flame detector.
4. The detector must be installed with a sunshade when it is installed under outdoor sunlight.
 
3. Basic functions of JTGB-UF-XSS665 infrared multi-parameter flame detector:

     JTGB-UF-XSS665 infrared multi-parameter flame detector is used in places with relatively high safety level. Compared with traditional point-type infrared flame detector products, this product has the characteristics of fast response, accurate judgment, high reliability, and strong anti-false alarm ability.

A715/IR3 Point Infrared Flame Detector Three-Band Infrared

 1. Function and composition of A715/IR3 point infrared flame detector

A715/IR3 point-type infrared flame detector can be used in places where flames (including partial smoldering fires) need to be monitored, quickly discovering flames that may cause fires, and issuing fire alarms in time.

A715/IR3 infrared flame detector converts flame combustion parameters into electrical signals through three infrared pyroelectric sensors working in different bands, and inputs the signals into industrial computing chips for comparison, calculation and analysis processing, and cooperates with special intelligent control software. Fire alarms are issued quickly and accurately.

The A715/IR3 infrared flame detector adopts a special aluminum die-cast flameproof housing, which has good explosion-proof and protective characteristics, corrosion resistance and aging resistance, and can work indoors, outdoors and various special industrial places for a long time.
2. A715/IR3 point type infrared flame detector shape structure and size

In order to meet the detector's long-term stable operation and explosion-proof requirements, the A715/IR3 uses an aluminum die-casting shell. The casing is divided into a shell and a bottom cover.

In order to ensure the explosion-proof performance, the shell and the bottom cover are connected by threads, and a rubber sealing ring is installed on the connection surface.

Both the wire inlet hole and the installation hook are set on the shell to facilitate the wiring operation.

A plastic inner shell is used to fix and protect the circuit part. Only three infrared flame sensors and indicator lights are exposed on the front panel of the inner shell, and only the wiring terminals are exposed at the rear to prevent damage to the circuit during installation and wiring.


 
3. Technical parameters of A715/IR3 infrared flame detector

1. Basic parameters of A715/IR3 point infrared flame detector

Item Specifications
Name Point Infrared Flame Detector
Model A715/IR3
Executive standard GB15631-2008 "Special Fire Detector"
●GB3836.1-2000 "Electrical Equipment for Explosive Gas Atmospheres" Part 1: General Technical Requirements
●GB3836.2-2000 "Electrical Equipment for Explosive Gas Atmospheres" Part 2: Flameproof "D"
Sensors Sharp Detection AE-S708/3, AE-S708/4 and AE-S708/5 Infrared Pyroelectric Sensors
Optical window white sapphire (Al2O3)
Housing ●Material: Aluminum alloy
●Molding process: Die casting
●Coating process: surface electrostatic powder spraying, internal metal passivation treatment
Weight ≤1kg
Explosion-proof and protection Explosion-proof: EXdⅡCT6
●Protection: IP66

2. Working parameters of A715/IR3 point infrared flame detector

Item Specification or Status
Power Supply Minimum Standard Maximum
18VDC (customizable 12VDC) 24VDC 30VDC
Working current Monitoring state ≤ 15mA, alarm state ≤ 35mA
Warm-up time 60s after power on
Fire alarm When a flame (including partial ignition fire) is found in the monitored area, the detector enters the fire alarm state;
The fire alarm output relay acts, and the red fire alarm indicator lights up
Fault alarm When the sensor, power supply, etc. are found to be abnormal, the detector enters the fault alarm state;
The fault output relay acts, and the yellow fault indicator lights up;
When fire alarm and fault occur at the same time, fire alarm takes priority;
Alarm threshold 1-5 levels adjustable (factory set to 3 levels)
The number of times the green light flashes each time in the monitoring state indicates the alarm threshold
Alarm delay 0-30s adjustable (factory set to 0s)
Drift compensation sensor hardware compensation and intelligent software compensation combined mode
It can effectively compensate the drift caused by temperature, environmental changes and long-term work of components
Interference source suppression Can effectively suppress the influence of non-flame interference sources, such as sunlight (direct and reflected), common artificial light sources, background radiation sources, hot moving objects, electric welding, etc.
Indicator light Monitoring status: green light flashing
●Fire alarm status: the red light is always on
●Fault status: the yellow light is always on
Output Fire alarm relay, action when alarming, output contact 1A@30VDC1A@250VAC
●Fault relay, action when fault occurs, output contact 1A@30VDC1A@250VAC
●4-20mA current loop
●Serial communication interface

4. Detection performance and protection range of A715/IR3 infrared flame detector

Maximum detection distance D(max)
Fire source situation A715/IR3 red ultraviolet flame detector maximum detection distance D(max)
Gasoline 0.1㎡ fire plate (0.3m*0.3m)

55m
n-heptane

55m
diesel fuel     

50m
kerosene

50m
aviation kerosene

50m
Alcohol     

50m
Isopropanone

50m
Methanol 45m
Polypropylene 20m
Paper 35m
Methane 0.5m(H)*0.2(w) gas flame 35m
LPG propane

  illustrate:

1. The central axis in the above figure is perpendicular to the detection window;

2. The vertical and horizontal directions of the detection area in the "Schematic Diagram of Detection Area" are consistent;

3. The above figure shows that the 100% position is the maximum detection distance D(max), and the detection distance of each angle can be obtained from the figure

4. Calculated by multiplying the percentage of the upper black edge by D(max);

5. The maximum detection distance D(max) in various environments is detailed in the above table
5. Environmental parameters of A715/IR3 point infrared flame detector

Item Specifications
Working temperature -10℃~+55℃
Working humidity ≤95%HR, no condensation
Storage temperature -20℃~+60℃

6. Setting and recording

Project Description
Setting Using PC and special software, the alarm parameters of the detector can be set through the serial communication port:
●Alarm mode
●Alarm threshold
●Alarm delay time
Professional operation and password authorization are required
Easy setting Use the magnet at hand to control the built-in reed switch to adjust the alarm sensitivity
Record query Using PC and special software, the internal record of the detector can be queried through the serial communication port
●Factory settings: alarm threshold, delay time.
●User settings (default factory settings): alarm threshold, alarm delay time.
●Factory functions: maintenance, calibration, compensation parameter information, qualified identification, software version, product ID, etc.
Professional operation and password authorization are required

7. Main circuit and software of A715/IR3 point infrared flame detector

The circuit part mainly includes sensors, low-noise amplifiers, industrial processing units, peripheral input and output and drive circuits, power supplies and EMC circuits, etc.


The MCU has built-in special software program, which uses Anyu's three-band infrared flame detection algorithm and criterion rules.

JTG-UM-GST9616 Flameproof Infrared Flame Detector

 1. Overview of JTG-UM-GST9616 point infrared flame detector:

JTG-UM-GST9616 point-type infrared flame detector (hereinafter referred to as the detector) is a compound infrared flame detector, which can judge the fire by detecting the light signal of the flame in the two bands of the infrared light region.

The detector is suitable for detecting the burning of open flames produced by carbonaceous materials. It is used in large spaces where flames are the main source of fire at the initial stage. It can be used indoors or outdoors.

This detector will not cause false alarms for interference from sunlight, artificial light sources, heat radiation, etc., and the work is stable and reliable.

The JTG-UM-GST9616 detector has two working modes: coded and non-coded. When working in coding mode, the detector can be directly connected to the fire alarm controller produced by Gulf Company in the form of a bus, and the detector obtains power from the bus and transmits information through the bus. When working in non-coding mode, the detector needs DC24V power supply to transmit information through the relay contacts.

This detector is an explosion-proof product, which can be used in general civil places and industrial hazardous places, such as Zone 1 and Zone 2 in explosive gas environments and Zone 21 and Zone 22 in combustible dust places.
2. Technical characteristics of JTG-UM-GST9616 point infrared flame detector:

1. Working voltage:

Coding mode: bus power supply, voltage range: DC16V ~ DC28V

Non-coding mode: DC24V power supply, voltage range: DC20V~DC28V

2. Working current:

Encoding mode: monitoring current ≤ 2mA, alarm current ≤ 4mA;

Non-coding mode: monitoring current ≤ 19mA, alarm current ≤ 35mA

3. Sensitivity level:

The detector has three sensitivity levels, which meet the requirements of GB15631-1995.

The factory setting of the detector is Class I sensitivity, which is the highest sensitivity. Users can reduce the sensitivity level according to the needs of the site. The sensitivity level of the detector can be changed on site by using the electronic encoder produced by Gulf Company.

4. Detection range:

The furthest detection distance of the detector corresponds to a level I sensitivity of 25m, a level II sensitivity of 17m, and a level III sensitivity of 12m. The corresponding relationship between detection distance and angle is shown in Figure 1, and the shaded part is the detectable range. The semicircle in the figure represents the detection distance, which is given as a percentage.


5. Response time ≤30s;

6. Indicator lights:

Red LED: Periodically flashes when in monitoring status, and keeps on when in fire alarm;

Yellow LED: off when monitoring status, always on when fault occurs;

7. Contact output:

1) When the detector works in encoding mode, the contact output is not used, and the contact signal is invalid.

2) When the detector works in non-coding mode, it has fire alarm contact output and fault contact output.

Fire alarm contact output: passive normally open contact, contact capacity is 1A/30VDC;

Fault contact output: passive normally open contact, contact capacity 1A/30VDC.

8. Use environment:

Temperature: -20℃~+55℃

Relative humidity: ≤95%, non-condensing

9. Protection level: IP66

10. Dimensions: 166mm×235mm×199mm (with adjustment frame)

11. Installation hole distance: 125.5mm×80mm

12. Shell material and color: stainless steel, metallic gray

13. Cable requirements:

1) Coding mode: connect to the controller bus, use RVS twisted pair with core section ≥ 1.0mm2;

2) Non-coding mode: Connect with DC24V power supply, use cables with core cross-section ≥ 1.0mm2, cable outer diameter of 8mm ~ 10mm, it is recommended to use cables with copper core multi-strand conductors;

3) It should meet the requirements of the use environment, such as explosion-proof, heat-resistant, corrosion-resistant, fire-resistant, etc.

14. Weight:

Detector 4.8kg

Adjustment frame 1.3kg

15. Explosion-proof mark: ExdIICT6/DIPA21TA, T6 explosion-proof certificate number: CNEx06.0429

16. Executive standard: GB3836.1-2000, GB3836.2-2000, GB12476.1-2000, GB15631-1995
3. Test of JTG-UM-GST9616 point infrared flame detector:

Warning: Please wait until all the detectors are installed before turning on the power, and then test after working for 60 seconds.

1. The detector must be tested after installation or after each regular maintenance.

2. Test content:

1) The detector in encoding mode should be able to be registered by the controller after it is powered on; the red indicator light should flash periodically when it is in the monitoring state; after the detector is powered on for 20 minutes, it will light up the infrared light at a distance of about 1.5m in front of it. The light source and the detector should alarm and light the fire indicator light within 30s; the controller can reset the detector to return to the normal monitoring state.

2) For detectors in non-coding mode, the red indicator light should flash periodically when it is powered on and in the monitoring state; after the detector is powered on for 20 minutes, ignite the infrared light source at a distance of about 1.5m in front of it, and the detector should transmit within 30s The fire alarm contact signal is issued and the fire alarm indicator light is lit.

3. For detectors in encoding mode, after the test, the controller sends a communication command to reset the detector and notify the relevant management department that the system returns to normal.

4. For detectors in non-standard mode, after the test, the power is cut off directly, and the relevant management department is notified that the system returns to normal.

5. During the test, the unqualified detectors should be cleaned according to "Maintenance" and then tested again. If they still fail to pass the test, they should be returned for repair.

JTH-CH381Ex point type infrared flame detector (three wavelengths)

 1. Performance characteristics of JTH-CH381Ex point infrared flame detector

Immunity to electromagnetic radiation, sunlight and background thermal radiation.

3.8uM, 4.4uM, 5.0-11.0uM three wavelength detection reduces false explosion rate.

Standard RS485 interface based on Modbus (RTU) protocol and 4~20mA output, alarm relay output.

It can be used in conjunction with the alarm controller, PLC, DCS and other systems produced by Xihe Caiqiao.

It adopts single-chip microcomputer processing system, which has strong stability and anti-interference ability and low power consumption.

Reverse protection function.
2. Technical parameters of JTH-CH381Ex point infrared flame detector
Model JTH-CH381Ex
Name Point Infrared Flame Detector
Brand Xihe Caiqiao
Spectral range 3.8um 4.4um 5.0um
Fire Sensitivity Level Ⅰ
Detection angle ≤120°
Rotation angle 180°
Signal transmission mode 4-20mA output, standard RS485 interface, alarm relay output
Working voltage 16~32VDC (rated: 24VDC)
Power consumption <2W
Temperature range -10℃~+55℃
Humidity range 0~95﹪RH (no condensation)
Pressure range 86KPa~106KPa
Shell material cast aluminum
Machine weight 1.6Kg
Protection class IP66
Mounting thread G3/4"
Dimensions 186mm*191mm*96mm
3. Installation and wiring of JTH-CH381Ex point infrared flame detector

 JTH-CH381Ex点型红外火焰探测器安装

VFD/S-LA880 optical section smoke detector linear beam infrared beam

 1. Overview of VFD/S-LA880 optical section smoke detector

Linear beam smoke detector (also known as optical cross-section smoke detector, divided into visualization and standard type, this model is the standard type) is an intelligent smoke detector, which uses optical cross-section image smoke detection Detection technology, consisting of transmitters and receivers, each receiver can correspond to multiple transmitters (the number of transmitters is determined according to the site conditions), can implement arbitrary curved surface coverage for the protected space, and has the ability to distinguish emission light sources and interference light sources Ability. It is composed of an image acquisition unit, an embedded intelligent fire analysis platform, etc., and realizes functions such as video acquisition, fire analysis, fire alarm, fault alarm, and video encoding transmission. Communication with the monitoring center through optical fiber Ethernet realizes intelligent analysis, distributed detection, networked transmission and centralized management. It is suitable for special places with large spaces such as tobacco warehouses, railway stations, and exhibition centers.
2. Functional characteristics of VFD/S-LA880 optical section smoke detector

Embedded intelligent fire analysis platform is adopted to realize distributed fire detection and centralized management;

Adopt image non-contact smoke detection, with long detection distance and large protection area;

Each receiver can correspond to multiple transmitters, and any curved surface coverage can be implemented for the protected area;

Adjustable multi-level sensitivity, strong environmental applicability, and anti-vibration interference ability;

Industrial appearance design, protection level up to IP65;

Strong compatibility, can be connected to conventional automatic fire alarm system;

Simple structure, easy maintenance and strong scalability.
3. Application places of VFD/S-LA880 optical section smoke detector

Exhibition Center, Conference Center

Airport terminals, railway waiting halls, hangars, moving garages

Gymnasium, sports center, theater

commercial atrium

Comprehensive pipe gallery, highway tunnel, industrial plant

Warehousing and logistics center

...
4. Technical parameters of VFD/S-LA880 optical section smoke detector

Optical section fire detector receiver technical parameters
Model VFD/S-LA880/R
Working voltage DC24 V±15%
Rated power ≤20W
Communication interface RJ45
Protection angle (H×V) 64°×50°
Detection distance 3~30m
Switch output: 1 fire alarm, 1 failure
Digital input 1 reset signal
Video resolution D1 (720×576), H.264
Support protocols TCP/IP, HTTP, RTSP
Working temperature -10℃~55℃
Working humidity ≤93%RH(40℃)
Air pressure 80KPa~106KPa
Dimensions 249 (length) × 158 (width) × 80 (height) (mm)
Weight 1.75Kg
Shell material aluminum alloy
Protection class IP65
Installation method wall mount, ceiling mount

Light section fire detector transmitter technical parameters
Model VFD/S-LA880/T
Working voltage DC24 V±15%
Rated power ≤5W
Working temperature -10℃~55℃
Working humidity ≤93%RH(40℃)
Air pressure 80KPa~106KPa
Dimensions 66 (L) × 106 (W) × 138 (H) (mm)
Weight 0.30Kg
Shell material ABS
Protection class IP65
Installation method wall mount, ceiling mount

JTY-HM-TX3703 Linear Beam Smoke Detector

 1. Overview of JTY-HM-TX3703 linear beam smoke detector

JTY-HM-TX3703 linear beam smoke detector is a coded reflective linear infrared beam smoke detector, and the detector must be used with a reflector.

The detector adopts a new and reasonable structural design, and is equipped with a unique laser module and digital tube indication during the debugging process, making the debugging process simpler. The detector can be used in shopping malls, fitness centers, gymnasiums, exhibition halls, museums, hotel lobbies, printing factories, garment factories, warehouses and other places.
2. Working principle of JTY-HM-TX3703 linear beam smoke detector

The detector is placed opposite to the reflector. The detector consists of two parts: transmitting and receiving. The transmitting part emits an infrared beam of a certain intensity. After being reflected by the reflector, the receiving part of the detector synchronously collects and amplifies the returned infrared beam, and the collected signal is processed by the built-in single-chip microcomputer. Analyze and judge. When the smoke enters the detection area, the intensity of the infrared light received by the receiving part decreases because the smoke blocks the light. After reaching the alarm threshold, the detector lights up the red indicator light and uploads the fire alarm signal through the bus.
3. Functional characteristics of JTY-HM-TX3703 linear beam smoke detector

Communication method: non-polar two bus

With automatic compensation function, it can automatically compensate for the influence caused by factors such as dust and vibration to a certain extent, which improves the reliability of the detector

Debugging is simple, there is a concentric laser module indication, you can easily find the optical path, and there is a digital tube display, which can indicate the intensity of reflected light

Sensitivity and distance values can be set on site through the hand-held encoder

Fully sealed protection process of PCB board

Support two application modes of coding and non-coding

HZ911 Linear Beam Smoke Detector

 1. Overview of HZ911 linear beam smoke detector

The HZ911 linear beam smoke detector is a long-range reflective linear infrared beam smoke detector. HZ911 linear light beam smoke detector is divided into two parts, the transmitter receiver and the reflector. The two parts of the detector are respectively installed on both sides of the detection space, facing each other. The transmitter emits a certain intensity infrared beam, which is received by the receiver and amplified synchronously, and then the collected signal is analyzed and judged by the built-in single-chip microcomputer. When the detector is in the normal monitoring state, the intensity of the infrared light received by the receiver is stable within a certain range; when the smoke enters the detection area, due to the scattering effect of the smoke on the light, the intensity of the infrared light received by the receiver decreases . When the smoke reaches a certain concentration and the intensity of the infrared light received by the receiver is lower than the predetermined threshold, the detector will report a fire alarm and the red working status indicator light will always be on.

HZ911 linear light beam smoke detector has a built-in single-chip microcomputer with excellent performance, which has powerful analysis and judgment capabilities. Through the calculation program solidified inside the detector, it can automatically complete the compensation for changes in external environmental parameters, fire alarm judgment and fault judgment, and The status indication is given through the indicator light and the signal output terminal.
2. Applicable places of HZ911 linear beam smoke detector

HZ911 linear light beam smoke detector adopts a new and reasonable structural design, which has strong anti-interference ability of ambient light, large protection space, easy installation and simple debugging. The detector can be used in historical buildings, warehouses, large storage areas, shopping malls, fitness centers, gymnasiums, exhibition halls, hotel lobbies, printing factories, garment factories, museums, prisons, etc., and can also be used in places with slight smoke and dust .
3. Places where HZ911 linear beam smoke detector is not suitable for use

1. Places with a ceiling height exceeding 40 meters;

2. Places with unsealed ceilings;

3. Places where the space height is less than 1.5 meters;

4. Places with a lot of dust, dry powder or water vapor;

5. Places with high temperature;

6. Places that cannot be maintained;

7. The detector is installed on the wall or the fixed object is greatly affected by the surrounding mechanical vibration;

8. Places with fixed or moving objects within 1 meter from the optical path of the detector;

9. Places with strong magnetic fields.
4. Technical parameters of HZ911 linear beam smoke detector
Model HZ911
Name Linear Beam Smoke Detector
Brand Hongzhen Electronics
Working voltage DC24V
Working current <20mA
Monitoring power <1W
Response threshold 1.9dB
Wire system Four-wire system (two power lines, two signal lines)
Output type Relay type (passive normally open, a group of faults; a group of alarms), address type
Maximum optical path direction deviation ±1º
Installation height 0.5m~1m from the top of the building
The maximum optical path length is 100m (more than 60m need to add a reflector), the minimum optical path length: 5m
The protection range is 7 meters on the left and right sides of the beam, that is, the distance between the two pairs of detectors is 14 meters
Ambient temperature -10℃~50℃
Relative humidity ≤95%(40℃±2℃)

JTY-H-JBF-VDC1382A Linear beam smoke detector

 1. Product features of JTY-H-JBF-VDC1382A linear beam smoke detector

1. JTY-H-JBF-VDC1382A linear optical beam smoke detector consists of two parts: transmitter, receiver and reflector.

2. The linear optical beam smoke detector itself has no address coding function, and needs to be connected with the relay module JBF4137 to access the system.

3. JTY-H-JBF-VDC1382A is suitable for fire prevention in large spaces.

4. There are two specifications for linear optical beam smoke detectors with a detection distance of less than 50 meters or 100 meters.

5. JTY-H-JBF-VDC1382A detector can provide passive switch alarm signal output.
2. Technical indicators of JTY-H-JBF-VDC1382A linear beam smoke detector
Model JTY-H-JBF-VDC1382A
Working voltage DC19-28V
Working current less than 15mA (including alarm state)
Working principle Reflective type, dimming type
Protection area 1400m2
Maximum optical path direction deviation 5 degrees
Dimensions 200mm×146mm×120mm(L×W×H)
Executive standard GB14003-2005 "Linear Beam Smoke Detector"
3. Structural features, installation and wiring of JTY-H-JBF-VDC1382A fire detector

1. The detector is non-addressing type, and it is connected with JBF4137 relay module.

2. The transmitter and receiver are integrated, and no wiring is required to connect with the reflector.

3. JTY-H-JBF-VDC1382A detector can provide passive switch alarm signal output.

4. The longest detection distance is ≤100 meters.

5. JTY-H-JBF-VDC1382A sets the matching impedance through the DIP switch. By default, the fifth bit is OFF, the sixth bit is ON, and the output is 4.6KΩ.


  illustrate:

1. The JBF4137 relay module (terminal 4) L1 and (terminal 5) L2 are connected to two buses.

2. (Terminal 1) connects to 24V+, (terminal 2) connects to 24V power supply -.

3. Connect the linear light beam smoke detector (terminal GND) to the power supply 24V-.

4. The linear light beam smoke detector (terminal out1, out2) is respectively connected to the JBF4137 relay module (terminal 6 or 7, terminal 9 or 10).
4. Precautions for JTY-H-JBF-VDC1382A fire detector

1. JBF-VPT3601A-E special debugging tools should be used for debugging.

2. It is necessary to ensure that the installation position of the detector and the reflector is accurately measured, and there must be no obstructions around the detector and within 50 cm of the optical path.

3. Detectors and reflectors should be installed on stable and reliable building surfaces. When the detection distance is less than 50 meters, a reflector is required to detect

4. When the distance is greater than 50 meters and less than 100 meters, two reflectors are required.

JTY-H-JBF4382 linear beam smoke detector

 1. Product introduction of JTY-H-JBF4382 linear beam smoke detector

JTY-H-JBF4382 linear beam smoke detector (hereinafter referred to as: detector) is a reflective bus addressing linear beam smoke detector, suitable for Jade Bird Fire 11SF, 51S series controllers. The fire alarm and fault signals are output through the relay, which can be connected with fire alarm controllers from different manufacturers. The detector is equipped with laser module and LED signal indication, the whole debugging process is convenient, fast and easy to operate.
2. Product features of JTY-H-JBF4382 linear beam smoke detector

●Reflective linear beam smoke detector, integrated design of transmitting and receiving;

●Switch signal output, compatible with any manufacturer's signal input module;

●Easy debugging, the laser module quickly locates the installation position of the reflector, and the LED indicates the signal strength;

●Adopt automatic gain control technology, automatic background signal compensation, strong anti-sunlight ability;

●Built-in microprocessor, full-featured self-diagnosis, disturbance automatic filtering technology;

●Two sets of independent step-by-step precision fine-tuning, easy adjustment of horizontal/vertical optical angle, and accurate calibration.
3. Main parameters of JTY-H-JBF4382 linear beam smoke detector
Working voltage power supply: DC18V~DC30V
Working current monitoring status: ≤15mA
Alarm state: ≤35mA
Fault state: ≤25mA
Debugging state: ≤25mA
Relay contacts Maximum voltage: DC30V, maximum current: 2A
Status indication Monitoring status: the red indicator light is flashing
Alarm status: the red indicator light is always on
Fault status: The yellow indicator light is always on
Debugging status: the green indicator light is flashing or always on
4. Precautions for installation of JTY-H-JBF4382 linear beam smoke detector

The normal operation of the detector requires a stable installation surface, and it should not be installed on a surface that is greatly disturbed by the surrounding mechanical vibration;

●When the detector is installed, it should prevent strong light sources such as sunlight and halogen lights from directly illuminating the receiver. The angle between the light source path and the detector light path should be greater than 5°;

The optical path of the detector needs to be unobstructed and there should be no fixed or moving objects within 1m around the optical path;

The detector should not be installed in places where there is a lot of dust or water vapor;

The distance between the detector installation and the side wall and ceiling must be greater than 0.5m;

Before the detector is installed, you should determine your own address to prevent the phenomenon of repeated codes;

●When the installation distance between the detector and the reflector is between 5m and 50m, two reflectors are required. When the installation distance is between 50m and 100m, 4 reflectors are required. When the reflectors are used in combination, they should be placed tightly, and there should be no gaps between the reflectors.

JTY-HW-9008 Linear Infrared Beam Smoke Detector

 1. Overview of JTY-HW-9008 linear infrared beam smoke detector

The JTY-HW-9008 linear infrared beam smoke detector is composed of a transmitter and a receiver. The distance between the transmitter and the receiver is 5~100 meters. When a fire occurs, the receiver will be reduced due to smoke. The amount of received light is converted into an electrical signal to confirm the occurrence of a fire. The biggest feature of the detector is to monitor the linear area to ensure accurate alarm before the fire spreads. The detector is matched with the fire alarm host produced by Shanghai Songjiang Feifan Electronics Co., Ltd. The receiver of this detector can use the electronic encoder to set the detector address, the detector address is 1~252. Receiver built-in input module, module to bus loop. The longest shooting distance is 100m, the distance between two pairs of detectors is 14m, and the detectors are 7m away from the left and right walls.
2. Features of JTY-HW-9008 linear infrared beam smoke detector

The receiver is equipped with an input module, a signal module and a bus loop.

Two bus system.

The longest shooting distance is 100m.

The distance between the two pairs of detectors is 14 meters, and the detectors are 7 meters away from the left and right walls.
3. Parameters of JTY-HW-9008 linear infrared beam smoke detector

Monitoring current: working current <3mA

Alarm/action current: working current<10mA

Wiring requirements

Transmitter power cord: BYJ line ≥ 2.5mm2

Receiver signal line: BYJ line ≥ 1.5mm2

Receiver power cord: BYJ line ≥ 2.5mm2

use environment

Temperature: -10℃~50℃

Relative humidity: ≤95% (40℃±2℃)

Dimensions mm: 86×100

Friday, July 28, 2023

JTY-HS-YKS4150 Linear Beam Smoke Detector

 1. Overview of JTY-HS-YKS4150 Linear Beam Smoke Detector

JTY-HS-YKS4150 linear light beam smoke detector is composed of a transmitter and a receiver in pairs, and is relatively installed at both ends of the protection space. It is a linear smoke detector for a certain concentration of smoke alarm. The detector has powerful analysis and judgment ability, completes system debugging, fire alarm judgment and fault judgment, and gives status indication through indicator light and signal output terminal. The detector also has the function of compensation according to the change of the external environment parameters, which reduces the requirement of the detector on the cleanliness of the site environment. There are six indicator lights on the receiver to indicate the strength of the received infrared light signal, which is convenient for engineering debugging.

JTY-HS-YKS4150 linear light beam smoke detector is addressed through the encoder, and the addressing range is 1 to 254; it can be directly used in conjunction with our company's fire alarm controller.

This product can be used in any place where smoke appears before the fire is formed, especially suitable for large spaces such as exhibition halls, warehouses, tunnels, large workshops, electrical tunnels, transformer rooms, switch stations, furniture stores, power stations, steel mills, etc. shelf, long-distance places. More sensitive to black smoke.
2. Parameters of JTY-HS-YKS4150 linear beam smoke detector
Model JTY-HS-YKS4150
Working voltage DC24V
Bus voltage 18-24V pulse
Addressing range 1~254
Bus wiring mode Two buses without polarity
Monitoring current ≤25mA
Alarm current ≤40mA
Environmental Conditions Temperature: -15℃へ+50℃; Humidity: ≤95%RH
Optical path orientation dependence angle ±1 degree
Detection distance 10mへ100m
Protection width diameter 10m
Dimensions Φ128mm×112mm
color ivory white
3. Protection area of JTY-HS-YKS4150 linear beam smoke detector

     This detector can effectively protect a cylindrical area, and its maximum protection area is: area = length 100m × diameter 10m.
4. Installation and wiring of JTY-HS-YKS4150 linear beam smoke detector

     Wiring: Make the diameter of the wire as thick as possible to avoid signal attenuation on the line. Large signal attenuation will easily cause unstable work. The signal line usually chooses RVS-2×1.5mm, and the power line usually chooses BV-2×2.5mm2 copper core wire, which is laid through a metal tube or a flame-retardant tube. Ensure the insulation, reliability, and moisture resistance of the line, especially pay attention to the connection of the joint part of the wire, which is generally welded, and do a moisture-proof treatment. Wiring avoids mixing with strong current lines. the

     Install:  

(1) It must be ensured that the infrared beam emitted by the transmitter can be received by the receiver, and no obstructions are allowed within 200mm of the connection line between the transmitter and the receiver.

(2). The detector should be installed where the smoke is most likely to enter the beam protection area. the

(3) The bases of the transmitter and receiver must be fixed on a vertical wall with no vibration at both ends, and the fixing is reliable and must not be loose.

JTY-HS-BK801 Linear Beam Smoke Detector

 1. Overview of JTY-HS-BK801 linear beam smoke detector JTY-HS-BK801 linear beam smoke detector is a long-range reflective beam smoke detector, which is designed for the fire protection requirements of open areas. standard. The detector consists of a transmitter/receiver combination unit and a reflector. When the smoke entering the area between the emitter/receiver and the reflector weakens the light signal received by the receiver, and the light reduction rate reaches the set threshold, the detector will send out an alarm signal. If the light beam is completely blocked, a fault signal will be generated. The detector has an automatic compensation function for the dust accumulated on the lens, and a compensation function for the influence of ambient light and sunlight. During the on-site debugging process, the detector can automatically display the working status of the on-site debugging through the status indicator. JTY-HS-BK801 linear beam smoke detector, after special intrinsically safe explosion-proof circuit design and special potting process, meets the technical requirements of the national intrinsically safe explosion-proof standard. The explosion-proof mark is ExibⅡBT6Gb. 2. Main technical indicators of JTY-HS-BK801 linear beam smoke detector Model JTY-HS-BK801 Ambient temperature -30℃~55℃ Relative humidity 10%~95%RH non-condensing Working voltage 12~32VDC Static power consumption ≤8mA/24VDC Detection distance 6-100m Alarm current ≤12mA/24VDC Single reflector size 100mm×122mm Detector installation distance 14m Number of reflectors 6-50m two pieces 6-100m four pieces Alarm output Fire alarm, fault relay contact, 4-20mA output Contact capacity 30V/2A

JDHW-1 (through-beam type) explosion-proof infrared beam smoke detector

 1. Overview of JDHW-1 (through-beam) explosion-proof infrared beam smoke detector

JDHW-1 (opposite beam) explosion-proof infrared beam smoke detector (referred to as detector) is a linear smoke detector, which is suitable for installation at both ends of the protection space and alarms for a certain concentration of smoke. This product can be used in places where smoke appears before a fire is formed, especially suitable for places with large spaces, high shelves, and long distances. More sensitive to black smoke. This product can be used together with fire alarm controllers from any manufacturer at home and abroad. It meets the requirements of GB3836 series standards.

The detector consists of a transmitter and receiver paired. The infrared beam emitted by the transmitter passes through the protected space and reaches the receiver. The smoke generated by the burning of the substance diffuses to the beam area, which weakens the radiation flux received by the receiver. When the radiation flux weakens to the predetermined smoke sensing action threshold, the receiver The output fire alarm information is transmitted to the fire alarm controller. The receiver of the detector is provided with six indicator lights indicating the strength of the signal, which is convenient for engineering debugging.
2. Working principle of JDHW-1 (opposite beam) explosion-proof infrared beam smoke detector

1. JDHW-1 explosion-proof infrared beam smoke detector is a linear smoke detector. The infrared beam emitted by the transmitter passes through the protected space and reaches the receiver. The smoke generated by the burning of the substance diffuses into the beam area, making the receiver The received radiant flux weakens, and when the radiant flux weakens to the preset smoke sensing action threshold, the receiver outputs fire alarm information and transmits it to the fire alarm controller.

2. There is an infrared light-emitting diode in the transmitter, which emits infrared light intermittently. Through the double-convex lens, an approximately parallel infrared beam is formed, which is received by the photosensitive diode in the receiver and converted into an electrical signal. After amplification and detection, it becomes a DC voltage. The magnitude of this DC level simulates the magnitude of the radiation flux of the infrared beam.

3. When a certain concentration of smoke enters the beam area and the DC level in the receiver drops to the action threshold, the signal line outputs a fire alarm signal, and the red confirmation light on the receiver lights up.

4. During use, if the detector window accumulates dust and other particles, the radiation flux of the infrared beam reaching the receiver will be weakened. In order to ensure that the smoke detection threshold of the detector is not affected, the detector uses hardware to perform initial value drift Automatic compensation so that dust etc. that build up slowly over a long period of time will not cause false alarms.

5. During debugging, if the transmitter and receiver are not aligned, the receiver receives a very small optical signal and outputs a fault signal. When entering the normal monitoring state, if the detector is completely blocked, the receiver first outputs a fault signal about 10 seconds later Output fire alarm signal.

6. There are six indicator lights on the receiver to indicate the strength of the signal, which is convenient for engineering debugging.
3. Technical features of JDHW-1 (opposite beam) explosion-proof infrared beam smoke detector
Explosion-proof mark Exd (ib) Ⅱ CT6
Working voltage DC15V~DC28V
Monitoring current ≤12mA
Action current ≤22mA
Detector status indication

Debug status: The green and yellow lights are solid or flashing in a specific pattern

Normal monitoring status: the red indicator light flashes periodically

Fire alarm status: the red indicator light is always on, and the yellow indicator light is off

Fault status: the yellow indicator light is always on, the yellow indicator light is always on, the detector reports a fire alarm after 20 seconds, and the controller lights up the red indicator light and turns off the yellow indicator light

The optical path is completely blocked: the detector reports a fault first and is always on
Protection area Maximum protection area 14×100=1400㎡, maximum width 14m
Detection distance 3~100(m)
use environment

Temperature: -20℃~+50℃

Relative humidity: ≤95% non-condensing
Atmospheric pressure 80kPa~110kPa
Inlet diameter 2-M22×1.5 (the number and size of the inlet diameter can be designed and produced according to the needs of users)
Dimensions 197×195×116 (mm)
color: red
Weight transmitter 2.5kg; receiver 2.6kg

JDHW (reflection type) explosion-proof infrared beam smoke detector

 1. Overview of JDHW (reflective) explosion-proof infrared beam smoke detector

JDHW (reflective) explosion-proof infrared beam smoke detector (hereinafter referred to as the detector) is a non-coded reflective linear infrared beam smoke detector. The detector must be used with reflectors, but it is necessary to use one or four reflectors according to the installation distance between the two.

The detector has a built-in single-chip microcomputer with excellent performance, which has powerful analysis and judgment capabilities. Through the calculation program solidified inside the detector, it can automatically complete system debugging, compensation for changes in external environmental parameters, fire alarm judgment and fault judgment. Indicator lights and signal output terminals give status indications. The detector adopts a new and reasonable structural design, sensitive adjustment, accurate positioning, beautiful appearance, easy installation, simple and convenient debugging method.

This product complies with the standards of GB3836.1-2000 "Electrical Equipment for Explosive Gas Atmosphere Part I General Requirements" and GB3836.1-2000 "Electrical Equipment for Explosive Gas Atmosphere Part II Flameproof Type "d"". It is suitable for fire monitoring in flammable and explosive places where smoke occurs in the primary stage of fire, with large areas, high racks, and long distances. It has passed the inspection by the inspection agency designated by the state and obtained a national explosion-proof certificate.
2. Features of JDHW (reflective) explosion-proof infrared beam detector

  1. Wide working voltage range and large protection area;

  2. The detector combines the transmitting part and the receiving part into one, and the installation is simple;

3. Built-in microprocessor, intelligent fire alarm and fault judgment;

4. With automatic calibration function. Debugging can be completed by a single person in a short time;

5. With self-diagnosis function, it can monitor the internal failure of the detector;

6. With automatic compensation function, it can automatically compensate for factors that reduce the received signal such as dust pollution, position offset and aging of the transmitting tube to a certain extent;

7. With fire alarm and fault passive output contacts;

  8. Two levels of sensitivity can be set on site;

  9. The detection optical path is ingeniously designed and has strong anti-interference performance;

10. Using SMT process;

11. The appearance is beautiful and generous.
3. Structural features of JDHW (reflective type):
Explosion-proof mark ExdⅡBT6
Temperature range -20℃~50℃
Humidity range less than 95%RH
Atmospheric pressure 80~110Kpa
Power supply voltage DCl5V--DC28V
supply current

Debug current≤20mA

Monitoring current≤12mA

Alarm current ~22mA
Fire alarm, fault contact output

Fire alarm relay: contact capacity 28V/2A, normally open in normal state, closed in fire alarm state

Fault relay: contact capacity 28V/2A, normally open in normal state, closed in fault state
Adjustment angle -6 degrees--+6 degrees
Optical path orientation dependence angle ±0.5 degrees
Sensitivity level

Level 1 sensitivity: the highest sensitivity

Secondary sensitivity: the lowest sensitivity
Detector status indication

Debug Status: The green and yellow LEDs are lit or flashed in a specific pattern, as described in the Debug section. Normal monitoring status: The red indicator light flashes periodically.

Fire alarm status: The red indicator light is always on, and the yellow indicator light is off. Need to power on again to clear the fire alarm.

Fault status: The yellow indicator light is always on. If the fault is restored, the fault signal of the detector is automatically eliminated by the detector.
The light path is completely blocked

The detector first reports a fault and lights up the yellow indicator light, and then reports a fire alarm after 20 seconds, lights up the red indicator light, and turns off the yellow indicator light.

Note: This situation does not mean that a fire has occurred. When the cover is restored, the fault signal is automatically cleared by the detector, and the fire alarm signal needs to be cleared by powering on again.
use environment

Temperature: -10℃--+50℃

Relative humidity ≤95%, non-condensing
Protection area The maximum protection area of the detector is 14x100=1400m2, and the maximum width is 14m
Optical path length 8m--100m
Dimensions 260×160×130mm
Installation size 185×140mm
Shell material aluminum alloy
color: red
Weight 3.7Kg

JTY-HM/F-GST102 Linear Beam Smoke Detector Reflector

 1. Overview of JTY-HM/F-GST102 linear beam smoke detector reflector: The JTY-HM/F-GST102 reflector is mainly used with the JTY-HM/F-GST102 linear beam smoke detector. 2. Structural features of JTY-HM/F-GST102 reflector: When the installation distance between the detector and the reflector is greater than or equal to 8m (less than or equal to 40m), a reflector needs to be installed; When the installation distance between the detector and the reflector is greater than 40m (less than or equal to 100m), four reflectors need to be installed. The installation of a single reflector needs to be fixed with two 6 plastic expansion nails. The installation dimensions are shown in Figure 1. When installing the four reflectors, they should be placed closely and there should be no gaps between the reflectors.

JTY-HM-GST9615 Flameproof linear beam smoke detector

 1. Overview of JTY-HM-GST9615:

JTY-HM-GST9615 linear beam smoke detector (hereinafter referred to as the detector) is a flameproof reflective linear infrared beam smoke detector. The detector has two signal output modes: bus output mode and contact output mode. When the detector is connected to the controller produced by Gulf Company, the status information between the two can be transmitted through the bus, and the detector itself can be encoded by the electronic encoder produced by Gulf Company, and the encoding range is between 1 and 242. When the detector is not connected with the controller produced by Gulf Company, the transmission of fire alarm and fault information can be completed through contact signals. The detector must be used in conjunction with the reflector, but it is necessary to use one or four reflectors according to the installation distance between the two.
2. Features of JTY-HM-GST9615:

1. The detector has a built-in single-chip microcomputer with excellent performance, which has powerful analysis and judgment capabilities. Through the calculation program solidified inside the detector, it can automatically complete system debugging, compensation for changes in external environmental parameters, fire alarm judgment and fault judgment. The detector is fully compatible with digital bus technology, and has the advantages of fast information upload speed and rich information content. The detector adopts a new and reasonable structural design, sensitive adjustment, accurate positioning, beautiful appearance, easy installation, simple and convenient debugging method. The sensitivity of the detector can be set on-site through the electronic encoder, which reduces the detector's requirements on the cleanliness of the site environment and broadens the application of this product.
2. This product complies with GB 3836.1 "Electrical Apparatus for Explosive Gas Atmospheres Part 1: General Requirements", GB 3836.2 "Electrical Apparatus for Explosive Gas Atmospheres Part 2: Flameproof "d"" and GB 14003 "Line Beam Sensitivity Smoke and Fire Detectors", GB 12476.1 "Electrical Equipment for Combustible Dust Environments Part 1: Electrical Equipment Protected by Housing and Limiting Surface Temperature Section 1 Technical Requirements for Electrical Equipment".
3. The detector is suitable for use in Zone 1 and Zone 2 with explosion-proof requirements in petroleum, chemical and other industries. It can work stably in harsh industrial environments and can be used in spaces with slight smoke and dust and corrosive gases.
Three, JTY-HM-GST9615 technical indicators:

1. Working voltage:

Bus voltage: 24V

Power supply voltage: DC24V

2. Working current:

Power supply current: debugging current ≤ 20mA

Monitoring current≤12mA

Alarm current≤22mA

Bus current ≤ 2mA (0mA when not connected with the controller produced by our company)

3. Fire alarm, fault contact output

Fire alarm relay: contact capacity 28V/2A, normally open in normal state, closed in fire alarm state

Fault relay: contact capacity 28V/2A, normally open in normal state, closed in fault state

4. Protected area:

The maximum protection area of the detector is 14×100=1400m2, and the maximum width is 14m

5. Explosion-proof mark: ExdIICT6/DIPA21TA, T6

6. Shell protection grade: IP66

7. Indicator lights:

Debug status: The green and yellow LEDs light up or flash in a specific way.

Normal monitoring status: The red indicator light flashes periodically.

Fire alarm status: When the detector reports a fire alarm, the detector fire indicator light is on, and the fire alarm relay is closed. When the detector is connected to the controller produced by our company, the fire alarm signal can be transmitted to the controller through the bus, and the fire alarm signal needs to be cleared by the controller; when the detector is not connected to the controller produced by our company, it needs to be reconnected Electrically clear the fire alarm message.

Fault status: The yellow indicator light is always on, and the fault relay is closed. If the fault is restored, the fault signal of the detector is automatically eliminated by the detector.

The optical path is completely blocked: the detector first reports a fault and lights up the yellow indicator light, and the fault relay closes; 20s later, the detector reports a fire alarm, lights up the red indicator light, and the fire alarm relay closes; the yellow light goes out, and the fault relay turns off. Note: This situation does not necessarily mean that a fire has occurred. When the fault signal does not turn into a fire alarm signal, if the block is restored, the fault signal will be automatically cleared by the detector.

8. Use environment:

Temperature: -20℃~+50℃

Relative humidity ≤95%, no condensation

9. Dimensions:

344mm×240mm×212mm (with adjustment bracket)

JB-QB-GST200H/2-S fire alarm controller high energy controller

 1. Overview of JB-QB-GST200H/2-S fire alarm controller (linkage type)

JB-QB-GST200H/2-S fire alarm controller/fire linkage controller (small point high-energy controller) is a new generation of fire alarm small point controller launched by Gulf Fire Company. In order to meet the needs of engineering design, this control The controller also has linkage control function and has powerful networking function. Multiple controllers can be networked to form a distributed fire alarm system.
2. Functional characteristics of JB-QB-GST200H/2-S fire alarm controller (linkage type)

◎Thin, 80mm thickness

◎The appearance and style are more professional

◎Suitable for installation in various environments

◎Built-in Bluetooth+USB debugging module, convenient management and debugging
3. Technical parameters of JB-QB-GST200H/2-S fire alarm controller (linkage type)
Model JB-QB-GST200H/2-S
Name Fire alarm controller/fire linkage controller
brand bay
Rated working voltage AC220V/50Hz
Battery 12V/5Ah, 2pcs
Equipment capacity 2 loops, each loop has 242 address points
Manual direct control output quantity 6 groups
printer has
Shell Material Metal
Dimensions 380mm×80mm×500mm

JB-QB-JBF-51S02 fire alarm controller

 1. Overview of JB-QB-JBF-51S02 fire alarm controller

JB-QB-JBF-51S02 controller is a new generation of small wall-mounted fire alarm controller (referred to as controller) host launched by Jade Bird Fire Protection Co., Ltd. The controller adopts a metal chassis structure, and the ultra-thin chassis structure design increases the application scenarios and scope of this product. It can be installed in-wall or conventional wall-mounted. It can be applied to large and medium-sized places, such as office buildings, high-end office areas, government libraries and other high-end places.
2. Functional characteristics of JB-QB-JBF-51S02 fire alarm controller

1) The two buses have no polarity and adopt address coding technology. The return line adopts the non-polarity wiring method of two buses, the building wiring is simple, the wiring paths and methods are arbitrary, and there is no order, which improves the wiring reliability, facilitates threading construction and line maintenance, and can greatly reduce the project cost.

2) LCD Chinese/English interface, can use the special software specially developed by Jade Bird Fire to make detailed Chinese 16 Chinese characters or 32 characters alarm address notes, and can display the specific equipment and alarm location of the fault or alarm, so that the displayed content It is clear at a glance, and the operation is convenient, clear and intuitive, realizing a good man-machine dialogue.

3) The system adopts distributed intelligent settings, and all matching field components have built-in microprocessors, thereby greatly reducing the amount of information transmission between the detector and the controller, and further improving the reliability of the fire alarm system.

4) Black box function. The controller has a built-in large-capacity memory, which can save various alarm information such as controller startup, shutdown, fire alarm, and fault. It is convenient for information query after the accident, and the information in the historical record can be printed out by time and type.

5) Strong anti-interference ability. Both hardware and software of the controller have good anti-interference measures, and the controller can operate normally and stably in an environment with strong electromagnetic interference.

6) Support no master-slave networking. It can support a network of up to 99 controllers at the same time, and can seamlessly network with various subsystem controllers of Jade Bird Fire.

7) The wall-mounted controller has a system capacity of 2 loops, a single loop supports a maximum of 252 points (62 protocols), and the system has a maximum of 504 points.

8) On-site linkage logic programming technology. Any logic programming of the controller can be realized, and the programming is simple and convenient.

9) In the networking mode, functions such as cross-controller linkage and setting automatic permission of other networked controllers can be completed, and the system composition is more flexible and the structure is more reasonable.
3. Technical parameters of JB-QB-JBF-51S02 fire alarm controller
Display operation unit 1
Display 4.3 inch color screen
Number of loops/components loaded 2 loops; 200 points/loop (11S protocol), 252 points/loop (62S protocol)
Manual direct control output 0 group
Manual bus linkage control output group 0
1 printer, serial port connection
2 relay contacts, passive output, 2 groups of fire alarm and fault normally open/normally closed adjustable, contact capacity 1A@24VDC
Communication interface 1 external CAN interface, 1 RS23 interface, 1 USB interface
Operating environment temperature -10°C~+50°C, relative humidity ≤95%
Storage environment temperature -20℃~+65℃, relative humidity ≤95%
Input voltage 220VAV, 50Hz/60Hz
Power capacity 3A@24VDC
External output 1A@24VDC (two outputs, of which output 2 is powered off for 3s with the reset of the alarm controller)
Backup battery 12VDC/2.8Ah, 2 pieces
Optional accessories JBF589X information interface card, 4G network card, Ethernet interface
Local machine address identification can be set through the local LCD screen interface
Dimensions L×W×H 340mm×80mm×460mm

JB-QB-JBF-51S01 fire alarm controller (linkage type)

 1. Overview of JB-QB-JBF-51S01 fire alarm controller (linkage type)

JB-QB-JBF-51S01 controller is a new generation of small wall-mounted fire alarm controller (referred to as controller) host launched by Jade Bird Fire Co., Ltd. The controller adopts a metal chassis structure, and the ultra-thin chassis structure design increases the application scenarios and scope of this product. It can be installed in-wall or conventional wall-mounted. It can be applied to large and medium-sized places, such as office buildings, high-end office areas, government libraries and other high-end places.
2. Functional characteristics of JB-QB-JBF-51S01 fire alarm controller (linkage type)

1) The two buses have no polarity and adopt address coding technology. The return line adopts the non-polarity wiring method of two buses, the building wiring is simple, the wiring paths and methods are arbitrary, and there is no order, which improves the wiring reliability, facilitates threading construction and line maintenance, and can greatly reduce the project cost.

2) LCD Chinese/English interface, can use the special software specially developed by Jade Bird Fire to make detailed Chinese 16 Chinese characters or 32 characters alarm address notes, and can display the specific equipment and alarm location of the fault or alarm, so that the displayed content It is clear at a glance, and the operation is convenient, clear and intuitive, realizing a good man-machine dialogue.

3) The system adopts distributed intelligent settings, and all matching field components have built-in microprocessors, thereby greatly reducing the amount of information transmission between the detector and the controller, and further improving the reliability of the fire alarm system.

4) Black box function. The controller has a built-in large-capacity memory, which can save various alarm information such as controller startup, shutdown, fire alarm, and fault. It is convenient for information query after the accident, and the information in the historical record can be printed out by time and type.

5) Strong anti-interference ability. Both hardware and software of the controller have good anti-interference measures, and the controller can operate normally and stably in an environment with strong electromagnetic interference.

6) Support no master-slave networking. It can support a network of up to 99 controllers at the same time, and can seamlessly network with various subsystem controllers of Jade Bird Fire.

7) The wall-mounted controller has a system capacity of 2 loops, a single loop supports a maximum of 252 points (62 protocols), and the system has a maximum of 504 points.

8) On-site linkage logic programming technology. Any logic programming of the controller can be realized, and the programming is simple and convenient.

9) In the networking mode, functions such as cross-controller linkage and setting automatic permission of other networked controllers can be completed, and the system composition is more flexible and the structure is more reasonable.
3. Technical parameters of JB-QB-JBF-51S01 fire alarm controller (linkage type)
Display operation unit 1
Display 4.3 inch color screen
Number of loops/components loaded 2 loops; 200 points/loop (11S protocol), 252 points/loop (62S protocol)
Manual direct control output 6 groups
Manual bus linkage control output 8 groups
1 printer, serial port connection
2 relay contacts, passive output, 2 groups of fire alarm and fault normally open/normally closed adjustable, contact capacity 1A@24VDC
Communication interface 1 external CAN interface, 1 RS23 interface, 1 USB interface
Operating environment temperature -10°C~+50°C, relative humidity ≤95%
Storage environment temperature -20℃~+65℃, relative humidity ≤95%
Input voltage 220VAV, 50Hz/60Hz
Power capacity 3A@24VDC
External output 1A@24VDC (two outputs, of which output 2 is powered off for 3s with the reset of the alarm controller)
Backup battery 12VDC/2.8Ah, 2 pieces
Optional accessories JBF589X information interface card, 4G network card, Ethernet interface
Local machine address identification can be set through the local LCD screen interface
Dimensions L×W×H 340mm×80mm×460mm

JB-TB-JBF-11SF-C8 fire alarm controller wall-mounted

 1. JB-TB-JBF-11SF-C8 fire alarm controller wall-mounted features

1) The two buses have no polarity and adopt address coding technology. The return line adopts the two-bus non-polarity wiring method, the building wiring is extremely simple, the wiring path and method are arbitrary, and there is no order, which improves the wiring reliability, facilitates threading construction and line maintenance, and can greatly reduce the project cost.
2) LCD Chinese/English interface, all displayed in Chinese/English. Various operations are prompted in the form of menus, and detailed alarm address annotations in 16 Chinese characters or 32 characters can be made through the specially developed software, which can display the specific equipment and alarm location of the fault or alarm, so that the display The content is clear at a glance, and the operation is convenient, clear and intuitive, realizing a good man-machine dialogue.
3) All connected field devices are embedded with microprocessors. Both the point-type photoelectric smoke detector and the point-type temperature-sensitive fire detector monitor the changes of field parameters in real time, and analyze and judge the collected field parameters through the microprocessor, thereby greatly reducing the communication between the detector and the controller. The amount of information transmission further improves the reliability of the fire alarm system.
4) Black box function. The controller has a built-in large-capacity memory, which can save various alarm information such as controller startup, shutdown, fire alarm, and fault. It is convenient for information query after the accident, and the information in the historical record can be printed out by time and type.
5) Strong anti-interference ability. Both hardware and software of the controller have good anti-interference measures, and the controller can operate normally and stably in an environment with strong electromagnetic interference.
6) Master-slave networking mode. It can support up to 99 controllers networking at the same time.
7) The wall-mounted controller has two system capacities of 1~4 circuits (C4) and 1~8 circuits (C8). Each circuit is fully loaded with 200 points, and the maximum system capacity is 800 points (C4) and 1600 points (C8).
8) Stand cabinet and piano table controllers have a system capacity of 1 to 32 loops, each loop is fully loaded with 200 points, and the maximum system load is 6400 points.
9) On-site linkage logic programming. Any logic programming of the controller can be realized, and the programming is simple and convenient.
10) In the networking mode, functions such as cross-controller linkage, setting of automatic fire extinguishing mode, and automatic permission of other networked controllers can be completed. The system composition is more flexible and the structure is more reasonable.
11) Has a strong supporting ability. It can be connected to the image display device in the fire control room, and can be networked with fire extinguishing controllers, fire door monitors, electrical fire monitoring equipment, fire equipment power monitoring systems, and other types of fire alarm controllers of Jade Bird Fire to realize all-round fire monitoring. Detect fires and carry out corresponding fire extinguishing functions.
2. JB-TB-JBF-11SF-C8 fire alarm controller wall-mounted technical parameters
Part name Specifications
Display operation unit 1
Display 7 inch color screen
Loop daughter card 1~8
Circuit / missing load quantity

1~8 loops, 200 points/loop

The maximum number of loads supported: 1600 points
1 multi-line control panel, 8 outputs
1 printer, serial port connection
2 relay contacts, passive output, contact capacity 1A@24VDC
The first one is the main fire output
The second is the total fault output
Communication interface 1. External CAN interface 1
2. One RS232 interface
3. One USB interface
4. Ethernet interface (Ethernet) 1
Operating environment Temperature: -10~55°C; relative humidity: ≤95%
Storage environment Temperature: -20~65℃; relative humidity: ≤95%
Input voltage AC220V, 50Hz/60Hz
Power capacity 5A@DC24V
External output 2A@DC24V
Backup battery (DC12V/7Ah)×2
Optional accessories Information interface card (JBF589X)
Local machine address identification Engineering personnel set up through the local LCD screen interface
Dimensions L×WxH:535×140×750mm

JB-LBZ2-HK8308 fire alarm controller (linkage type)

 1. Overview of JB-LBZ2-HK8308 fire alarm controller (linkage type)

Hikvision's new generation of fire alarm control linkage equipment can receive and send out fire alarm signals and fault signals, complete the corresponding display and linkage control functions, and support the transmission of alarm and fault information to the monitoring center and various comprehensive security platforms of our company system. The product has the characteristics of strong performance, high reliability, flexible configuration, and convenient installation and use, so that the product can meet the needs of a variety of different scenarios, from small-scale engineering scenarios to large-scale buildings, and has universal adaptability.
2. Technical parameters of JB-LBZ2-HK8308 fire alarm controller (linkage type)
Model JB-LBZ2-HK8308
Name Fire alarm controller, fire linkage controller
Brand Hikvision
Working voltage AC220V 50Hz
Equipment capacity up to 8 circuits
Loop capacity 250 address points per loop
Battery 12V 17Ah, 2pcs
Display LCD screen
printer has
Shell Material Metal
Dimensions 810mm×510mm×160mm

JB-QB-Z-A101 Fire Alarm Controller Wall Mounted

 1. Features of JB-QB-Z-A101 Fire Alarm Controller

The two buses have no polarity and adopt address coding technology.
LCD Chinese interface, all displayed in Chinese characters.
The controller has a built-in large-capacity memory, which can save various information such as controller startup, shutdown, fire alarm, and fault.
Strong anti-interference ability.
The slave unit network mode can support up to 99 controllers at the same time.
The controller has a single loop, and the loop is fully loaded with 252 points.
On-site linkage logic programming technology, programming is simple and convenient.
It has a strong matching ability, and can be connected with a model fire alarm controller to form a network to realize all-round fire monitoring.
2. Technical parameters of JB-QB-Z-A101 fire alarm controller
Working temperature 0~+40℃
Storage temperature -20~+65℃
Relative humidity ≤95% (no condensation)
Main power supply AC220V (+10%, -15%), 50Hz
Backup power DC24V,(12V/2.8Ah)X2
Power consumption ≤30W
Fire alarm relay 1 passive output, electric shock capacity DC30V/2A
Fault relay 1 passive output, electric shock capacity DC30V/2A
System capacity Single loop 252 points
Communication distance 1500m
Manual control output 6 groups
Wire system Two-wire system (non-polarity)
Inspection cycle ≤3 seconds
Communication/data interface 1xRS232 interface, 1xUSB interface, 1x external CAN interface, 1x485 interface
Shell material Main body: galvanized sheet Display: 2.8 inch color screen
Dimensions 300mm(L)×88mm(W)×380mm(H)
Implementation standard GB4717-2005 "Fire Alarm Controller"

JB-TBL-8600 fire alarm controller (linkage type) Weston

 1. Overview of JB-TBL-8600 fire alarm controller (linkage type)

JB-TBL-8600 fire alarm controller (linkage type) and fire detectors and modules form an automatic monitoring and control system to monitor the fire and smoke conditions on site, use intelligent algorithms to judge its status (fire alarm or fault or feedback), and complete automatic fire alarm and linkage functions. The controller adopts bus communication, and integrates alarm, monitoring and control in the same loop bus. The hardware circuit is controlled by a single-chip microcomputer, the layout is simple and compact, and it is easy to install and expand. The appearance of the controller is wall-mounted, with full Chinese LCD display, novel and beautiful in appearance, and it is a high-performance, high-reliability intelligent fire alarm controller (linkage type).
2. Technical parameters of JB-TBL-8600 fire alarm controller (linkage type)
Model JB-TBL-8600
Name Fire alarm controller, linkage controller
Brand Weston Central Electronics
Power supply AC220V±50Hz
Backup power supply DC 24V (2 sealed batteries: 12V/4Ah)
Machine capacity 2 circuits × 254 points = 508 points
Loop capacity Two-wire intelligent smoke detector, temperature detector, manual alarm button, input module, linkage module, etc., any combination of up to 254 points
direct output

6 groups of contact relay active output, contact capacity 1A/24VDC, output current 500mA
Power output 1 set of 24V power output, output capacity 1A/24V
Operating environment temperature -10℃~+50℃
Relative humidity ≤95%
Dimensions 450mm×370mm×120mm
Executive standard GB4717-2005, GB16806-2006

JB-QB-NT8009 fire alarm/fire linkage controller

 1. Overview of JB-QB-NT8009 fire alarm/fire linkage controller

With the increasing demand for product configuration in the market, Nite continues to explore technology upgrades and launches a new generation of JB-QB-NT8009 fire alarm controller/fire linkage controller, small size, large capacity, high reliability, integrated fire alarm, fire protection Linked together to bring a new product experience.

In order to fully meet the diverse product needs of customers, Nite has fully optimized the appearance and size of the new generation of JB-QB-NT8009 fire alarm controller/fire linkage controller, and re-layouted the panel design. The thickness of the host is only 84mm, and the volume is smaller. The weight is only one-third of the original, and it supports wall-mounted and wall-mounted installations. The operation is more convenient and the installation space is greatly saved.

The new generation of JB-QB-NT8009 fire alarm controller/fire linkage controller adopts advanced technologies such as non-polarity two buses, full digital transmission, CPU high-speed processing, intelligent algorithm, etc., with digital display, threshold tracking, adjustable sensitivity, alarm Points and linkage points can be randomly mixed, intuitive operation, convenient debugging and other outstanding advantages, in line with GB4717-2005 "fire alarm controller" national standard.
2. Features of JB-QB-NT8009 fire alarm/fire linkage controller

1. Double circuit design, with a total capacity of 504 points, unlimited types, and can be connected to various detectors, modules, fire display panels, etc.
2. It comes with a 2-point bus disk, which can start two devices at the same time without inputting codes, which is easy to operate and use.
3. Newly added self-test button, event confirmation button, and stop indicator light, which are more intuitive to the operating status of the device.
4. The multi-line panel button has changed from one to two, and the distinction between start and stop is clearer.
5. The linkage start button is optimized. When the controller is in the manual state, when a fire occurs, one-button start can be completed without switching to automatic.

 外形尺寸

JB-QB-JF999X wall-mounted fire alarm controller

 1. Introduction of JB-QB-JF999X wall-mounted fire alarm controller

According to the national standard GB4717-2005 "Fire Alarm Controller" and GB16806-2006 "Fire Linkage Control System", the two-bus intelligent fire alarm intelligent fire automatic alarm and fire linkage controller is fully in line with GB50116-2013 "Fire Automatic Alarm System Design Specifications" 》Requirements for the controller. The total number of devices connected to each loop is ≤200 points, and it is very convenient to set the alternate loop playback of fire alarm and fire emergency broadcast through the controller.

5-inch color LCD display, full Chinese interface. Various operations are prompted in the form of menus, and detailed alarm address notes in 16 Chinese characters or 32 characters can be displayed, and the specific equipment and alarm location of the fault or alarm can be displayed, so that the display content is clear at a glance, and the operation is convenient, clear and intuitive. Good realization of man-machine dialogue function.

Black box functionality. The controller has a built-in large-capacity memory, which can save various information such as controller startup, shutdown, fire alarm, fault, start and stop of linkage equipment, etc. for a long time. It is convenient to inquire after the event, and the information in the historical record can be printed out by time, type, etc.

The connected field components are all embedded with microprocessors, and the point-type smoke detectors and point-type temperature detectors monitor the changes of field parameters in real time, and the field component microprocessors analyze and judge the collected field parameters, thereby The amount of information transmission between the detector and the controller is greatly reduced, and the reliability of the fire alarm system is further improved.

Large system capacity. A single controller has 1 to 64 loops, each loop can be fully loaded with 200 on-site components, and can be connected to 15 fire display panels, with a total of 12,800 on-site component points. Each controller can carry 12 multi-line linkage control panels and 8 bus linkage control panels.

No master-slave networking mode. Multiple controllers can be networked, and the controllers in the network are not divided into hosts and extensions. An alarm from one controller can be responded to by other controllers at the same time. It can realize 99 controllers to form a network, and the maximum transmission distance of the network is 1.5km, so that a very large alarm system can be formed.

On-site linkage logic programming technology. Any logic programming of the controller can be realized, and the programming is simple and convenient. In the network mode, cross-controller linkage can be completed, and the system composition is more flexible and the structure is more reasonable.

Supporting ability is strong. It can be connected with various supporting equipment such as gas fire extinguishing control, graphic display device in fire control room, etc.
2. Technical parameters of JB-QB-JF999X wall-mounted fire alarm controller
Wire system Two bus lines, no polarity
System capacity The system adopts a single loop, with a maximum capacity of 100 bus addressing points and 15 pieces of liquid crystal layer display
Operating environment Temperature: 0℃~40℃; Relative humidity: 93±3% (40±2℃)
Power main power: AC220V (+10%, -15%), 50Hz; backup power: DC24V 2.8Ah
Detector power supply 24V pulse mode
Display mode 5-inch LCD screen, 800×480 resolution, Chinese and English interface switching
Loop bus transmission distance The longest transmission distance is 1000 meters, and the cross-sectional area of the conductor is ≥1.5mm² multi-strand copper core soft wire
Historical records Classified storage, up to 4000 pieces of information can be stored (including 1000 pieces of fire alarm information)
Implementation standard GB4717-2005 "Fire Alarm Controller"

JB-QB-FS5101 fire alarm controller

 1. Features of JB-QB-FS5101 fire alarm controller

● 32-bit Cortex-M3 core processor, the system runs at high speed, stable and reliable;

● Support U disk to read/backup programming data, which is convenient for system debugging;

● The fire alarm bus adopts a highly reliable all-digital bus communication protocol, mainly including non-destructive bus information arbitration technology, double verification and real-time interactive verification communication technology, and multi-access cluster automatic ID identification technology;

● Strong EMC anti-interference design and anti-surge design 3 sets of multi-line control output, used to control fire pumps, exhaust fans and other important fire-fighting equipment;

● Event "black box", which can record more than 10,000 events, and will not be lost when power off;

● With powerful self-adaptation and self-diagnosis functions, it is convenient for engineering debugging, bus fault analysis and daily maintenance;

● Applicable to various small industrial and civil buildings such as hotels, residences, industrial plants, and entertainment venues.
2. Technical parameters of JB-QB-FS5101 fire alarm controller
Implementation standard GB4717-2005 "Fire Alarm Controller"
Structural form Wall-mounted, L385mm×W285mm×H85mm
Main power supply AC187V~242V, 50Hz (±1Hz)
Backup power supply DC12V3Ah lead-acid battery two
Switching power supply DC30V 2.3A power supply
Bus parameters Bus voltage: 18V ~ 30V Drive current: 500mA
Bus 1.5km (cross-sectional area ≥ 1.5mm2)
Capacity: 250 points per circuit
Controlled 24V DC24V 500mA
Output interface Fire alarm relay, fault relay
Printer Micro thermal printer
Weight 7.0kg
Expansion interface Optional expansion card (CAN networking and RS485, 4G or Ethernet)
Operating environment 10℃~50℃, -20℃~60℃10RH%-95%RH (no condensation)

JB-TB-V6852 fire alarm controller (linkage type)

 1. Overview of JB-TB-V6852 fire alarm controller

JB-TB-V6852 type fire alarm controller (wall-mounted) is a wall-mounted sub-type controller of the cabinet type and piano type v6852 controller, which has all the characteristics and technical characteristics of the cabinet type and piano type controller. The wall-mounted V6852 controller can independently constitute a fire alarm and linkage control system, which is suitable for smaller-scale fire alarm and fire linkage projects, and can also be used as a node of a fire alarm multi-machine network control system to distribute to scattered large-scale buildings In order to avoid risks such as insufficient terminal voltage and mutual interference between lines caused by the long-distance laying of too many loop buses.

The wall-mounted V6852 controller also has a wealth of interface resources, which can be used to connect with other manufacturers' fire emergency broadcasting, fire telephone, emergency evacuation instructions and other systems, as well as other automatic monitoring and management systems.
2. Technical parameters of JB-TB-V6852 fire alarm controller
Working main voltage AC220V/50HZ
Spare battery specification 7AH/12V, 2 pieces
Loop output voltage DC 15V~28V
Number of loops 8 loops
Loop capacity 200 address points
Working environment temperature -10℃~50℃
Ambient relative humidity ≤95%RH (40±2°C)
Manual direct control output 8 groups
Manual bus control output 16 groups
Linkage power output DC24V/2A
Machine size Width 480mm x thickness 122mm x height 355mm

 尺寸图

JB-QBL-HA9001 fire alarm controller/fire linkage controller (wall-mounted)

 1. Features of JB-QBL-HA9001 fire alarm controller/fire linkage controller

The system loop line adopts two-wire communication power supply technology, non-polarity, and the network wiring is simpler

The host screen is displayed in Chinese characters on a color LCD screen, which is convenient for query and the content is clear at a glance

The rapid reporting of fire alarm information wins precious time for fire alarm, fire fighting and rescue

On-site linkage logic programming is flexible, which can realize a variety of customized linkage requirements, programming is simple and convenient, and reduces the workload of debugging

External ports include RS485 and 1 fire alarm output
2. Technical parameters of JB-QBL-HA9001 fire alarm controller/fire linkage controller
Main power supply AC220V ±15%, 50Hz
Backup power supply 12V7Ah 2 sections
Bus disk 48 points
Multi-line disk 6 points
LCD screen 7.0-inch TFT color LCD screen, resolution 800×480
Working environment Temperature: 0℃~+40℃, relative humidity: ≤95%RH, no condensation
Maximum loop 1
Up to 240 points
Dimensions (L)440mm×(W)533mm×(H)125mm

JB-TB-FlexES fire alarm controller

 1. Overview of JB-TB-FlexES fire alarm controller

FlexES series fire alarm control system is an intelligent fire alarm system launched by Germany Anshe Company. Based on a mature technology platform and system framework, the system strictly follows Anshe's global unified quality standards, and is jointly developed by German and Chinese technical teams to provide comprehensive and leading fire alarm solutions for customers who place emphasis on safety and quality. Suitable for large hotels, commercial buildings, hospitals and other important places.

Compared with previous controllers, the FlexES series has more powerful performance, faster speed, and more convenient debugging and installation. It has powerful networking capabilities and supports up to 64 controllers to be connected to the network. At the same time, it also inherits the high quality and high technology of German ESSER, and retains modular design, redundant technology, intelligent detectors and modules and other equipment. The new generation of FlexES fire alarm controller is an excellent interpretation of our breakthrough in traditional industrial design.

The E98-PLUS fire alarm controller under the FlexES series integrates alarm and linkage control, and meets the dual items of GB4717-2005 "General Technical Conditions for Fire Alarm Controllers" and GB16806-2006 "General Technical Conditions for Fire-fighting Linkage Control Equipment" Standard testing requirements.
2. System features of JB-TB-FlexES fire alarm controller

JB-TB-FlexES火灾报警控制器系统特点

JB-TB-FlexES Fire Alarm Controller System Features

Ansher FlexES bus is a 2-wire loop technology (ring wiring) with power supply and monitoring at both ends. It uses unshielded twisted pair, and each circuit can carry 127 equipment components, and the total length of the circuit is 3.5 kilometers. A loop can be divided into up to 127 detection areas. Even if a breakpoint occurs at any point on the loop, the bus loop can still maintain normal operation; when a short circuit occurs in the loop, the built-in short-circuit isolator of the detector will automatically divide the loop into several sections , to isolate the short-circuit segment from the rest of the circuit.

The Anshe FlexES bus can divide the detectors and manual alarm buttons into areas. In addition to the detectors, it can also be connected to the Anshe FlexES intelligent input and output modules and wireless detectors.

The intelligent input and output modules on the Anshe FlexES bus provide input and output interfaces for the monitoring and control of remote equipment. All devices use factory coding technology. FlexES can automatically identify the structure of the circuit and determine the address of each bus unit. The hardware address of the device does not need to be set by dialing codes or using an address encoder on site.

Anshe FlexES bus protocol is used to monitor the bus and unit wiring, and communicate all alarm, fault, maintenance and service information according to priority.

JB-QBL-DH1025 fire alarm controller (linkage type)

 1. Overview of JB-QBL-DH1025 fire alarm controller

The JB-QBL-DH1025 fire-fighting main engine is mainly used in new construction, reconstruction, and expansion of small and medium-sized projects with automatic fire alarm systems. It can be used with other Dahua automatic fire alarm system node equipment (such as smoke detectors, fire manual Alarm buttons, fire sound and light alarms, input and output modules, etc.) products are used together, and flexibly configured to form a fire linkage control system to realize fire detection, alarm and linkage control of fire prevention and fire extinguishing systems to ensure building fire safety. The controller uses a 4.3-inch true-color LCD screen, includes a printer, includes 2 12V/5Ah batteries for backup power, includes 16 groups of bus control buttons, and includes 7 groups of direct control buttons. It can directly access the Shixiao cloud platform through Ethernet and 4G (requires additional 4G module DH-HY-PN01 and 4G IoT card).
2. Functional characteristics of JB-QBL-DH1025 fire alarm controller

1. The information is reported quickly, and the first alarm reporting time is less than 1 second;

2. Simple debugging, configuration information can be imported through U disk;

3. Easy to network, can access the platform through 4G and RJ45 interfaces;

4. The system adopts non-polarity two-wire system, which is simple in construction and saves wiring.
3. Technical parameters of JB-QBL-DH1025 fire alarm controller
Model JB-QBL-DH1025
Name Fire alarm controller Linkage controller
Brand Dahua
Working voltage AC220V/50Hz
Rated power 84W
Output voltage Bus output rated voltage: DC24V
Backup power 2 x 12 V/7 Ah lead-acid batteries
Load capacity The bus can carry 500 node devices, 16 control points on the bus disk, and 7 groups of control points on the direct control disk
Storage capacity 9999 historical records
Display mode 4.3 inch color LCD
Communication mode Two bus
Platform access 4G, Ethernet
Networking method RS485
Coding range 1~254
Communication distance <1500 meters
Communication interface USB, RJ45, CAN, RS232, RS485, 1 fire alarm output, 1 fault output and DC24V
color: White
Shell material Chassis: cold-rolled steel SPCC
Panel ABS
Corrosion protection level low
Protection class IP30
Working temperature –10℃~+55℃
Storage temperature –20℃~+65℃
Working humidity ≤95% RH (no condensation)
Installation method Wall-mounted
Product size 330mm×115mm×480mm (length×width×height)
Certification type CCC certification
Implementation standard GB4717-2005; GB16806-2006