Friday, July 28, 2023

JB-TB-JBF-11SF-C8 fire alarm controller wall-mounted

 1. JB-TB-JBF-11SF-C8 fire alarm controller wall-mounted features

1) The two buses have no polarity and adopt address coding technology. The return line adopts the two-bus non-polarity wiring method, the building wiring is extremely simple, the wiring path and method are arbitrary, and there is no order, which improves the wiring reliability, facilitates threading construction and line maintenance, and can greatly reduce the project cost.
2) LCD Chinese/English interface, all displayed in Chinese/English. Various operations are prompted in the form of menus, and detailed alarm address annotations in 16 Chinese characters or 32 characters can be made through the specially developed software, which can display the specific equipment and alarm location of the fault or alarm, so that the display The content is clear at a glance, and the operation is convenient, clear and intuitive, realizing a good man-machine dialogue.
3) All connected field devices are embedded with microprocessors. Both the point-type photoelectric smoke detector and the point-type temperature-sensitive fire detector monitor the changes of field parameters in real time, and analyze and judge the collected field parameters through the microprocessor, thereby greatly reducing the communication between the detector and the controller. The amount of information transmission further improves the reliability of the fire alarm system.
4) Black box function. The controller has a built-in large-capacity memory, which can save various alarm information such as controller startup, shutdown, fire alarm, and fault. It is convenient for information query after the accident, and the information in the historical record can be printed out by time and type.
5) Strong anti-interference ability. Both hardware and software of the controller have good anti-interference measures, and the controller can operate normally and stably in an environment with strong electromagnetic interference.
6) Master-slave networking mode. It can support up to 99 controllers networking at the same time.
7) The wall-mounted controller has two system capacities of 1~4 circuits (C4) and 1~8 circuits (C8). Each circuit is fully loaded with 200 points, and the maximum system capacity is 800 points (C4) and 1600 points (C8).
8) Stand cabinet and piano table controllers have a system capacity of 1 to 32 loops, each loop is fully loaded with 200 points, and the maximum system load is 6400 points.
9) On-site linkage logic programming. Any logic programming of the controller can be realized, and the programming is simple and convenient.
10) In the networking mode, functions such as cross-controller linkage, setting of automatic fire extinguishing mode, and automatic permission of other networked controllers can be completed. The system composition is more flexible and the structure is more reasonable.
11) Has a strong supporting ability. It can be connected to the image display device in the fire control room, and can be networked with fire extinguishing controllers, fire door monitors, electrical fire monitoring equipment, fire equipment power monitoring systems, and other types of fire alarm controllers of Jade Bird Fire to realize all-round fire monitoring. Detect fires and carry out corresponding fire extinguishing functions.
2. JB-TB-JBF-11SF-C8 fire alarm controller wall-mounted technical parameters
Part name Specifications
Display operation unit 1
Display 7 inch color screen
Loop daughter card 1~8
Circuit / missing load quantity

1~8 loops, 200 points/loop

The maximum number of loads supported: 1600 points
1 multi-line control panel, 8 outputs
1 printer, serial port connection
2 relay contacts, passive output, contact capacity 1A@24VDC
The first one is the main fire output
The second is the total fault output
Communication interface 1. External CAN interface 1
2. One RS232 interface
3. One USB interface
4. Ethernet interface (Ethernet) 1
Operating environment Temperature: -10~55°C; relative humidity: ≤95%
Storage environment Temperature: -20~65℃; relative humidity: ≤95%
Input voltage AC220V, 50Hz/60Hz
Power capacity 5A@DC24V
External output 2A@DC24V
Backup battery (DC12V/7Ah)×2
Optional accessories Information interface card (JBF589X)
Local machine address identification Engineering personnel set up through the local LCD screen interface
Dimensions L×WxH:535×140×750mm