JTY-HS-YKS4150 Linear Beam Smoke Detector

 1. Overview of JTY-HS-YKS4150 Linear Beam Smoke Detector

JTY-HS-YKS4150 linear light beam smoke detector is composed of a transmitter and a receiver in pairs, and is relatively installed at both ends of the protection space. It is a linear smoke detector for a certain concentration of smoke alarm. The detector has powerful analysis and judgment ability, completes system debugging, fire alarm judgment and fault judgment, and gives status indication through indicator light and signal output terminal. The detector also has the function of compensation according to the change of the external environment parameters, which reduces the requirement of the detector on the cleanliness of the site environment. There are six indicator lights on the receiver to indicate the strength of the received infrared light signal, which is convenient for engineering debugging.

JTY-HS-YKS4150 linear light beam smoke detector is addressed through the encoder, and the addressing range is 1 to 254; it can be directly used in conjunction with our company's fire alarm controller.

This product can be used in any place where smoke appears before the fire is formed, especially suitable for large spaces such as exhibition halls, warehouses, tunnels, large workshops, electrical tunnels, transformer rooms, switch stations, furniture stores, power stations, steel mills, etc. shelf, long-distance places. More sensitive to black smoke.
2. Parameters of JTY-HS-YKS4150 linear beam smoke detector
Model JTY-HS-YKS4150
Working voltage DC24V
Bus voltage 18-24V pulse
Addressing range 1~254
Bus wiring mode Two buses without polarity
Monitoring current ≤25mA
Alarm current ≤40mA
Environmental Conditions Temperature: -15℃へ+50℃; Humidity: ≤95%RH
Optical path orientation dependence angle ±1 degree
Detection distance 10mへ100m
Protection width diameter 10m
Dimensions Φ128mm×112mm
color ivory white
3. Protection area of JTY-HS-YKS4150 linear beam smoke detector

     This detector can effectively protect a cylindrical area, and its maximum protection area is: area = length 100m × diameter 10m.
4. Installation and wiring of JTY-HS-YKS4150 linear beam smoke detector

     Wiring: Make the diameter of the wire as thick as possible to avoid signal attenuation on the line. Large signal attenuation will easily cause unstable work. The signal line usually chooses RVS-2×1.5mm, and the power line usually chooses BV-2×2.5mm2 copper core wire, which is laid through a metal tube or a flame-retardant tube. Ensure the insulation, reliability, and moisture resistance of the line, especially pay attention to the connection of the joint part of the wire, which is generally welded, and do a moisture-proof treatment. Wiring avoids mixing with strong current lines. the

     Install:  

(1) It must be ensured that the infrared beam emitted by the transmitter can be received by the receiver, and no obstructions are allowed within 200mm of the connection line between the transmitter and the receiver.

(2). The detector should be installed where the smoke is most likely to enter the beam protection area. the

(3) The bases of the transmitter and receiver must be fixed on a vertical wall with no vibration at both ends, and the fixing is reliable and must not be loose.