Friday, July 28, 2023

JB-TBL-8600 fire alarm controller (linkage type) Weston

 1. Overview of JB-TBL-8600 fire alarm controller (linkage type)

JB-TBL-8600 fire alarm controller (linkage type) and fire detectors and modules form an automatic monitoring and control system to monitor the fire and smoke conditions on site, use intelligent algorithms to judge its status (fire alarm or fault or feedback), and complete automatic fire alarm and linkage functions. The controller adopts bus communication, and integrates alarm, monitoring and control in the same loop bus. The hardware circuit is controlled by a single-chip microcomputer, the layout is simple and compact, and it is easy to install and expand. The appearance of the controller is wall-mounted, with full Chinese LCD display, novel and beautiful in appearance, and it is a high-performance, high-reliability intelligent fire alarm controller (linkage type).
2. Technical parameters of JB-TBL-8600 fire alarm controller (linkage type)
Model JB-TBL-8600
Name Fire alarm controller, linkage controller
Brand Weston Central Electronics
Power supply AC220V±50Hz
Backup power supply DC 24V (2 sealed batteries: 12V/4Ah)
Machine capacity 2 circuits × 254 points = 508 points
Loop capacity Two-wire intelligent smoke detector, temperature detector, manual alarm button, input module, linkage module, etc., any combination of up to 254 points
direct output

6 groups of contact relay active output, contact capacity 1A/24VDC, output current 500mA
Power output 1 set of 24V power output, output capacity 1A/24V
Operating environment temperature -10℃~+50℃
Relative humidity ≤95%
Dimensions 450mm×370mm×120mm
Executive standard GB4717-2005, GB16806-2006