1. Features of JTW-ZOM-HK8003 point-type temperature-sensitive fire detector
Built-in high-performance ultra-low power consumption microprocessor, fast operation speed and reliable performance.
Non-polarity two buses, convenient for construction and wiring, and avoid equipment failure caused by wrong connection.
The fire alarm confirmation light is transmitted by a light guide column and can be seen at 360°.
High reliability sensor design, can adapt to high humidity basement and other environments.
Intelligent temperature rise compensation algorithm improves the response ability under different temperature rise conditions.
2. Technical parameters of JTW-ZOM-HK8003 point-type temperature-sensitive fire detector
Executive standard GB 4716-2005 "Point Type Heat Sensing Fire Detector"
Installation method Use with HK-DZ-8001 detector base
Working Environment Temperature: -10 °C~50 °C
Relative humidity: ≤95%, non-condensing
Product size Φ100 mm × H 49 mm (with base)
Device weight 92g
1 indicator light, red (flashing for inspection, always on for alarm)
Power consumption Monitoring current ≤200 uA; alarm current ≤400 uA
Encoding parameters Special electronic encoder encoding
Wire system non-polar two bus
Rated operating voltage DC 24 V
Bus voltage DC 24 V (DC 18 V ~ DC 28 V)
Wiring requirements RVS 2 × 1.5 mm2, maximum distance: 1000 m