The Series 65 Optical Smoke Detector includes a pulsed LED located in the detector housing. The outer detector is molded the same as the ionization detector and has an indicator LED that is clear at rest but produces a red light in alarm.
The 65 Series Optical Smoke Detector uses the principle of scattered light to detect smoke entering the smoke chamber of the detector.
1. Responds well to slow-burning, smoke-producing fires
2. Suitable for bedrooms and escape routes
3. Not affected by wind or atmospheric pressure
4. Alarm indicator light and magnet operation test switch option
Detection principle photoelectric
Optical maze An infrared emitter and sensor arranged radially to detect scattered light
Sensor Silicon PIN photodiode
Emitter Infrared LED
Inspection frequency 3s/time
Confirmation frequency 2s/time
Wire system Two-wire system, no polarity
Terminal block Power input connection L1 IN terminal and L2 terminal
Power output connection L1 OUT terminal and L2 terminal
Remote Indicator Negative Connection - R Terminal
Power supply voltage 9~33Vdc
Pulse voltage peak value is 2V (0.1Hz~100kHz)
Quiescent current 30~50μA(24V)
Pulse current 115μA (24V)
Indicator voltage 6~28V
Alarm current 61mA(28V);52mA(24V);18mA(10V)
Alarm indicator light red light in alarm state
Alarm current 4mA
Alarm threshold 0.15dB/m measured according to EN54-7 standard
Working temperature -20~60℃
Relative humidity 0~95%RH (non-condensing)
Atmospheric pressure and wind speed have no effect
Protection class IP23D
Implementation standards EN 54-7, LPCB, VdS, DIBt, BOSEC, FG, CPR and SBSC
Dimensions Φ100mm*H42mm (including base H50mm)
Color and terminal material UL94-V0 white, nickel-plated stainless steel
Weight 150g (including base)